INSTALLING THE OUTDOOR UNIT

Auxiliary Circuit Breaker

Outdoor unit

Distribution

board

 

Auxiliary power s/w

Auxiliary circuit breaker should be installed near outdoor unit so that each access is possible. Main/outdoor power supply cable are connected to upper/lower terminal of auxiliary circuit breaker.

It is necessary that the conduit kit for power supply to the outdoor unit be installed between auxiliary power S/W and the outdoor unit. (the conduit kit is optional)

The designs and shape are subject to change according to the model.

Electrical Work

1The supply voltage must be the same as the rated voltage of the air conditioner.

2Prepare the power souce for exclusive use with the air conditioner.

3Use 15 amperes time delay fuse or circuit breaker.

MODEL

AS07A5(A6)MA

 

AS09A5(A6)MA

 

AS12A5(A6)MC

 

 

 

 

 

 

 

 

 

 

Power supply

115V~/60Hz

 

 

115V~/60Hz

 

208-230V~/60Hz

 

 

 

 

 

Single phase

 

 

Single phase

 

 

Single phase

 

 

 

 

 

 

 

 

 

 

Power cable

 

 

 

 

3G AWG 14

 

 

 

 

 

 

 

 

 

 

 

Assembly cable

 

 

 

 

4G AWG 16

 

 

 

 

 

 

 

 

 

 

 

Operating current(C)

6.4

 

 

 

8.5

 

 

6.1

 

 

 

 

 

 

 

 

 

 

Starting Current

32A

 

 

47A

 

 

31A

 

 

 

 

 

 

 

 

 

 

Power consumption (C)

680W

 

 

900W

 

 

1320W

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

AS12AA(AB)MC

AS18A5(A6)RC

AS18A9(A0)RCD

AS24A1(A2)RC

 

 

 

 

 

 

 

 

 

 

Power supply

208-230V~/60Hz

208-230V~/60Hz

208-230V~/60Hz

208-230V~/60Hz

 

 

Single phase

 

Single phase

Single phase

Single phase

 

 

 

 

 

 

 

 

 

Power cable

 

 

 

 

3G AWG 14

 

 

 

 

 

 

 

Assembly cable

4G AWG 16

 

5G AWG 16

6G AWG 16

 

 

 

 

 

 

 

 

 

Operating current(C)

5.4

 

 

 

8.6A

8.0A

 

10.5A

 

 

 

 

 

 

 

 

 

Starting Current

31A

 

 

 

35A

37A

 

10.5A

 

 

 

 

 

 

 

 

Power consumption (C)

1230W

 

 

1900W

1770W

 

2350W

 

 

 

 

 

 

 

 

 

 

When using the special NFB, use the NFB to bear the capacity of the air conditioner.

E-38

Otherwise, the shot circuit in the NFB may occur.

 

Page 38
Image 38
Samsung AS18A9(A0)RCD, US12AA(AB)MC, US12A5(A6)MC, US18A5(A6)RC, US18A9(A0)RCD Auxiliary Circuit Breaker, Electrical Work