Electrical Specifications

󲧩

󲧩󲧩

󲧩HIP-205BE11, -205BE11-BO2, -200BE11, -200BE11-BO2, -195BE11,

-195BE11-BO2, -190BE11, -190BE11-BO2, -186BE11, -186BE11-BO2,

-180BE11, -180BE11-BO2 )

Model HIP
-205 BE11,
-205 BE11-BO2
HIP
-200BE11,
-200BE11- BO2
HIP
-195 BE11,
-195 BE11-BO2
HIP
-190BE11,
-190BE11- BO2
HIP
-186 BE11,
-186 BE11-BO2
HIP
-180BE11,
-180BE11- BO3
Cell Number in Series [Piec es] 96 96 96 96 96 96
Maximum Power (Pmax) [W] 205 200 195 190 186 180
Maximum Power Voltage (Vmp) [V] 56.7 55.8 55.3 54.8 54 .4 54.0
Maximum Power Current (Imp) [A] 3.62 3.59 3.53 3.47 3.42 3 .33
Open Circuit Voltage (Voc) [V] 68.8 68.7 68.1 67.5 67 .0 66.4
Short Circuit Current (Isc) [A] 3.84 3.83 3.79 3 .75 3.71 3.65
Cell Type
Maximum System Voltage [V] 1000 1 000 1000 1000 1000 1000
Factory Inst alled Bypass Diode Ye s Yes Yes Yes Yes Yes
Weight [kg] 14 14 14 14 14 14
HIT* (hybrid of a-Si and mono c- Si)
Electrical Spec ification
*HIT= Hetero junction with Intrinsic Thin-layer
Note: The values in the above table are nominal.
4Printed in Europe 20.10.2006

Module wiring

> The maximum number of HIP- xxxNHE5, xxxNHE5-BO2
modules that can be wired in series is seventeen (17).
> The maximum number of HIP-
󲨹󲨹󲨹
BE11, xxxBE11-BO2
modules that can be wired in series is thirteen (13).
> When your PV system includes other components
(batteries, charge controllers, inverters, etc.), be sure to
follow the safety recommendations of their manufactures.
> These modules contain factory installed bypass diodes.
If these modules are incorrectly connected to each other,
the bypass diodes or cable or junction box may be
damaged.

Array Wiring

The term “array” is used to describe the assembly of
several modules on a support structure with associated
wiring.
Use copper wire that is sunlight resistant and is insulated
to withstand the maximum possible system open circuit
voltage. Check your local codes for requirements.

Electrical Protection

The HIP- xxxNHE5, -xxxNHE5-BO2,
--xxxBE11, -xxxBE11-BO2 Module complies with the
requirements of Electrical protection Class II.
If necessary, the module or array can be grounded.

Module Terminations

A junction box as terminal enclosure is equipped for
electrical connections on SANYO modules.
The HIP- xxxNHE5, -xxxNHE5-BO2, -xxxBE11, -
xxxBE11-BO2 modules are equipped with MC plugs as
terminal enclosure.
Use these MC plugs for electrical connections.
Please contact your local dealer with questions
regarding other electrical connections for modules.
negative ( -) positive ( + )

Figure3: Configuration of

junction box

Connector
(MC Plug)
Cable

Junction box configuration and

description of terminals (for reference)

Modules equipped with one junction box contain
terminals for both positive and negative polarity, and
bypass diodes.
Two terminals are dedicated to each polarity (with the
polarity symbols engraved onto the body of the junction
box ) (see Fig3).