4. ELECTRICAL WIRING
Max. 130 m
2.5 mm2

4. ELECTRICAL WIRING

4-1. General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and cir- cuit breaker for overcurrent protection should be provided in the exclusive line.

(3)To prevent possible hazards from insulation fail- ure, the unit must be grounded.

(4)Each wiring connection must be done in accor- dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.

(5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

(7)Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before begin- ning.

You must ensure that installation complies with all relevant rules and regulations.

(8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.

Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

(9)If the power supply cord of this appliance is dam- aged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit

 

(A) Power supply

Time delay fuse or

 

Wire size

Max. length

circuit capacity

SPW-CR254GV(H)56-C

4 mm2

24 m

25 A

SPW-CR364GV(H)56-C

4 mm2

22 m

25 A

SPW-CR484GV(H)56-C

6 mm 2

30 m

35 A

Indoor unit

(B) Power supply Time delay fuse or circuit capacity

10

Control wiring

(C) Inter-unit (between outdoor and

(D) Remote control wiring

(E) Control wiring for group control

indoor units) control wiring

 

 

 

 

 

0.75 mm2 (AWG #18)

0.75 mm2 (AWG #18)

0.75 mm2 (AWG #18)

Use shielded wiring*

Use shielded wiring

Use shielded wiring

Max. 1,000 m

Max. 500 m

Max. 500 m (Total)

 

 

 

NOTE

* With ring-type wire terminal.