DeviceNet Communication Adapter
1.2.1Exec. V. 1.10 vs. V. 1.20
Exec. V. 1.20 changed the behavior of certain I/O bases if a field side fault occurred. This change affects the following bases.
H170 ADM 350 10
H170 ADM 350 11
H170 ADM 390 10
H170 ADM 370 10
The following table describes the differences between the two versions in more detail. Refer to the TSX Momentum I/O Base User Guide (870 USE 002 00) for module specifications.
Table 3 Exec. V. 1.10 vs. V. 1.20
Firmware | Module | Action |
|
|
|
| 170 ADM 350 10 | If one of the field side outputs faults |
| (shorts out), the host will read all inputs | |
| 170 ADM 350 11 | |
| as zeros, regardless of the input signal | |
| 170 ADM 370 10 | |
| state. | |
|
| |
|
|
|
|
| If one of the field side outputs faults |
Version 1.10 |
| (shorts out), the host will read all inputs |
| as zeros, regardless of the input signal | |
|
| |
| 170 ADM 390 10 | state. |
| If an open condition exists (unconnected) | |
|
| |
|
| on any of the input points, the host will |
|
| read all inputs as zeros, regardless of the |
|
| input signal state. |
|
|
|
| 170 ADM 350 10 | If one of the field side outputs faults |
| 170 ADM 350 11 | (shorts out), the host will continue to read |
| 170 ADM 370 10 | the inputs normally. |
|
|
|
|
| If one of the field side outputs faults |
Version 1.20 |
| (shorts out), the host will continue to read |
| the inputs normally. | |
| 170 ADM 390 10 | If an open condition exists (unconnected) |
| on any of the input points, the host will | |
|
| |
|
| read |
|
| H open inputs as zero (fault) and |
|
| H remaining |
|
|
|