DeviceNet Communication Adapter

1.2Specifications

Table 1 General Specifications

Description

Specification

ODVA compliance

Complies with ODVA Specification Release 2.0 for group 2

 

only slave supporting polled and strobed connections.

Data rate

Supports 125/250/500 Kbaud standard DeviceNet rates.

Network power loading

Voltage: Operational from 11 ... 25 Vdc.

 

Current drain: 110 mA maximum, 75 mA typical.

Required enclosure

Adapter is considered open equipment, requires enclosure

 

according to application.

Environment, RFI, EMI

Adapter conforms to the specification for the I/O base upon

 

which it is mounted. See the Momentum I/O Bases User

 

Manual, 870 USE 002 00 for I/O base specifications.

 

 

Agency approval

ODVA Certification

 

UL 508, 746C, 94

 

CSA 22.2 No. 142

 

CE Mark

 

FM Class 1 Div 2 Groups A, B, C, D

Table 2 Environmental Specifications

Description

Reference

Specification

Temperature, Operating

IEC 68–2–14

0 ... 60_C ambient

Temperatore, Storage

IEC 68–2–14

–40 ... 85_C

 

Humidity

IEC 68–2–3

95% RH at 60_C non–condensing

Altitude

MIL–STD–810

15

000 ft

 

Vibration, Operating

IEC 68–2–6

10

... 57 Hz:

0.075 mm DA

 

 

57

... 150 Hz:

1 g

Shock, Operating

IEC 68–2–27

15 g, 11 ms, 3 shocks/axis

Free Fall, Unpackaged

IEC 68–2–32

0.1 m

 

Free Fall, Packaged

IEC 68–2–32

24 in

 

3

Page 5
Image 5
Schneider Electric 170 LNT 710 00 manual General Specifications Description