Schneider Electric 3BZ2, iFBZ, FBZ2, EOCR-i3BZ manual Modbus network setting, RS485 bus connection

Models: EOCR-i3BZ FBZ2 iFBZ 3BZ2

1 22
Download 22 pages 21.33 Kb
Page 19
Image 19

Communication Guide

Modbus network setting

Communication setting value

Please set the Modbus communication parameters by PCON or HMI for the communication. Slave address

Baud rate Parity

Communication loss timeout

Slave address

The EOCR has slave addresses from 1 to 247.

The factory default setting is 1.

Baud rate

The Communication speed provided is like below. 1.2kbps

2.4kbps 4.8kbps 9.6kbps 19.2kbps 38.4kbps

The factory default setting is 19.2kbps

Parity setting

Even Odd None

The factory default setting is even. Please refer to the table for the stop bit setting.

Parity setting

Stop bit

Even or Odd

1

None

2

Communication loss timeout

It is the criteria to confirm the communication disconnection with a master like as PLC. EOCR judges it as a communication disconnection error, if there is no call from the master during a certain preset time.

The time setting range is 1~999sec the factory default setting is OFF. The OFF means no communication error check. It is advised to set it at OFF, if there is no concern of communication disconnection or no needs of communication error check at ordinary times.

RS485 bus connection

RS485 standard allows several different characteristics. Polarization

Line terminator Number of slaves Length of the bus

There is a definition of Modbus presented in detail at the website of Modbus.org in 2002. Standard connection.

19

Page 19
Image 19
Schneider Electric 3BZ2, iFBZ, FBZ2, EOCR-i3BZ manual Modbus network setting, RS485 bus connection