Communication Guide
Bus connection through a SCA type junction box
1. Master (PLC, PC or communication module)
2. Modbus cable (It is different according to the master side or a master having polarization combined to the other part of Bus)
3. Junction box
4. Modbus cable
5. Line terminators : 120- 0.25W
Please use a cable with 2pair shieded twisted conductors for Interface protection.
It is adviced to isolate the Modbus cable 30cm(11.8in) at least from a power cable.
If necessary, intersect the Modbus cable to a power cable perpendicularly.
Refer to the diagram in the left side for the line terminator wiring.
2 wire MODBUS RJ45 connections
Pin S can be used for shield wire connection.
Pin on RJ45 Pin on nEOCR EIA/TIA 485 name
4 D1 B/B
5 D0 A/A
8 V- C/C