Schneider Electric 3BZ2, iFBZ, FBZ2 Trip cause indication and fault records, Control terminals

Models: EOCR-i3BZ FBZ2 iFBZ 3BZ2

1 22
Download 22 pages 21.33 Kb
Page 15
Image 15

EOCR-i3BZ/iFBZ/3BZ2/FBZ2

EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,

EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT

Trip cause indication and fault records

3 fault records including the trip cause and 3phase currents are stored in a non-volatile memory.

Trip Indication

 

Trip

 

Indication after trip with UP/ DN button pressing

Trip Cause

Indication

Contents of Indication

L1 LED on

L2 LED on

L3 LED on

Over current

 

OC Trip caused by r-phase current

 

 

 

Phase loss

 

Phase Loss caused by r-phase lost

 

 

 

Reverse Phase

 

Phase reversal trip

 

 

 

Stall

 

Stall trip during motor starting

 

 

 

 

caused by s-phase current

 

 

 

 

 

 

 

 

Jam

 

Jam trip during motor running

 

 

 

 

caused by r-phase current

 

 

 

 

 

 

 

 

Imbalance

 

Imbalance trip caused by t-phase

 

 

 

 

current

 

 

 

 

 

 

 

 

Under Current

 

Under current trip caused

 

 

 

 

by s-phase current

 

 

 

 

 

 

 

 

Earth Fault

 

Earth Fault(Earth leakage) trip with

 

 

 

 

Earth Fault current indication

 

 

 

 

 

 

 

 

Limitation of auto-Reset

 

In 30minutes, the number of

For emergency restart, manual reset by pressing

 

 

auto-reset exceeds the pre-set count

ESC clears the reset counter to zero.

 

 

 

 

Control terminals

A type

 

 

 

 

 

 

 

 

 

GR

 

OL

 

OL

COMM

A1

A2

57 58

95

96

97

98

V- D1 D0 S

 

 

 

 

 

 

 

Modbus Communication

Control Power

 

 

 

 

 

 

OL NO Output

 

 

 

 

 

 

 

GR NO Output

 

 

 

 

 

 

OL NC Output

C type

 

 

 

 

 

 

AL /UL /TO

OL / GR

 

 

COMM

 

A1 A2 07 08 95

96

97

98

V-

D1 D0

S

Control Power

 

 

 

 

 

Modbus Communication

 

 

 

 

 

 

AL/UL/TO

 

 

 

 

 

OL/GR NO/NC Common Output

15

Page 15
Image 15
Schneider Electric 3BZ2, iFBZ, FBZ2, EOCR-i3BZ manual Trip cause indication and fault records, Control terminals