EOCR-i3BZ/iFBZ/3BZ2/FBZ2

EOCR-i3BZ / iFBZ : Intelligent Digital Over-Current, Earth Fault Relay with built-in ZCT,

EOCR-3BZ2 / FBZ2 : Economic Digital Over-Current, Earth Fault Relay with built-in ZCT

Setting sequence and menu

No.

Menu

 

Parameter

Description

 

Default

 

 

 

 

 

 

Threshold of Alert output, set by % of the over current threshold (oc). If the load

 

 

 

 

 

 

 

 

 

current is higher than this value, alert output(07-08 contact) is energized

 

 

 

 

 

 

 

 

 

according to the setting of “ALo:XX”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the load current is detected, alert output(07-08 contact) is energized. The alert

 

 

 

 

 

 

 

 

 

threshold is no meaning for this operation.

 

 

 

 

 

 

 

 

 

Refer to the Alert Operation Pattern.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the load current is higher than the alert threshold, alert output(07-08 contact)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

repeats open for 1s and close for 1s (flickering), The flickering starts from the

 

 

 

 

 

 

 

 

 

 

 

 

22

Alert *1)

 

 

 

 

motor starting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to the Alert Operation Pattern.

 

 

 

 

 

 

 

 

 

If the load current is higher than the alert threshold, alert output(07-08 contact) is

 

 

 

 

 

 

 

 

 

closed (holding) and remains closed until the load current decrease under the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alert threshold. The alert output is blocked during motor starting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to the Alert Operation Pattern.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the accumulated running hour is more than the Running Hour threshold,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the alert output repeats close for 1s and open for 1s.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The alert output is used only for under current protection. If this mode is selected,

 

 

 

 

 

 

 

 

 

a trip by an under current fault is signaled through alert output(07-08), instead of

 

 

 

 

 

 

 

 

 

overload trip output(95-96 or 97-98).

 

 

 

 

 

 

 

 

 

 

 

 

Fault reset by a power cycle or by pressing the ESC button.

 

 

Fault reset only by pressing the ESC button.

 

23

Reset

 

 

 

 

Fault reset by a auto-reset timer,

 

 

 

Setting range of the timer : 0.5sec~20min.

 

 

 

Also the fault can be reset by a power cycle or by ESC button.

 

 

 

The maximum auto-reset number during 30 minutes in auto-reset mode.

 

24

Reset Limitation

The auto-reset counter is stored in the non-volatile memory and is cleared by

 

pressing ESC button when the counter reaches the limitation.

 

 

 

 

 

 

To disable limitation, select “oFF”. Setting range : oFF~5 times.

 

 

 

In this menu, toggle display, “-trh-” and the accumulated value, is activated.

 

25

Total Running Hour

The accumulation starts from the installation and the user cannot clear the

Not

accumulated value.

adjustable

 

 

 

 

This display unit is 1 hour.

 

 

 

In this menu, toggle display, “--rh-” and the accumulated value, is activated The

 

 

 

user can clear the accumulated value by selecting the running hour threshold to

 

26

Running Hour

“rh:oFF”. When motor stops

Not

This display unit is 0.1 hour (6 minutes).

adjustable

 

 

 

 

By selecting “ALo:to”, the user can get the alert signal through alert output(07-08)

 

 

 

when the accumulated value is more than the running hour threshold.

 

 

Running Hour

Threshold for alert output when the user selects “ALo:to”. The unit is 10 hours

 

27

and this menu is not displayed when the motor is starting or running.

 

Threshold

 

 

Setting range : 10~9990 hours, oFF

 

 

 

 

 

 

Modbus slave address.

 

 

 

Range : 1 ~ 247.

 

 

 

Setting for Communication speed

 

 

 

Range : 1.2kbps, 2.4Kbps, 4.8Kbps, 9.6Kbps,19.2Kbps, 38.4Kbps .

 

28

Communication*2)

Parity setting

 

 

 

Range : odd, even, non.

 

 

 

Duration for communication loss detection.

 

 

 

Displays alarm when no new communication data is received for the duration.

 

 

 

If “oFF” is selected, no monitoring for communication channel is activated.

 

 

 

Setting range : 1~999 sec, oFF

 

 

 

When this menu activated, OL trip signal and enabled EF trip signal is generated

 

 

 

when (3s+ot) expires. The display shows “End” when the test is done.

 

29

Test Trip

By pressing ESC, returns to the load current display mode.

No

This menu is not displayed when the motor is starting or running.

parameter

 

 

 

 

Before (3s+ot) expires, pressing ESC or motor starting or running blocks the test

 

 

 

trip and return to the load current display.

 

30

End

This shows the end of test trip. Test result is stored in the fault record.

No

parameter

 

 

 

*1) This menu is only available in “C” Type.

*2) These are applied to i3BZ & iFBZ only.

14

Page 14
Image 14
Schneider Electric EOCR-i3BZ, iFBZ, FBZ2, 3BZ2 manual Menu Parameter Description Default, Alert *1, Communication *2