LEAK CHECKING A CHARGED SYSTEM
ABOUT PRESSURES
Refrigerant in a saturated condition, part liquid and part vapor will exert a pressure that is a function of its temperature. The higher the temperature, the higher the pressure. Avoid leak checking in cold weather.
A refrigerant leak will show with moderate pressure. A leak is not a function of pressure. Pressure is only required to aid in detection.
In cold weather, it is possible to raise the pressure in the system by warming the cold plate with a light bulb left in close proximity to the cold plate for several hours with the box lid open.
There are two ways to
1.Soap bubbles (a solution of dish soap and water works well).
2.
TO LEAK CHECK WITH BUBBLES
Soap each connection and observe all sides of the connection with a bright light and a mirror. A leak will blow bubbles. Without careful examination and plenty of pressure this test is not reliable.
TO LEAK CHECK WITH AN ELECTRONIC DETECTOR
Use a detector designed for
IF A LEAK IS DETECTED
If a leak is detected try tightening the fitting nut slightly more. (See Swagelok fittings). If the leak is not stopped, it is possible that the fitting was assembled incorrectly. Discharge the system, and then disconnect the fitting for inspection. After reassembly, proceed to the leak check procedure.