Sears EF12F1900A2, EF20N2600A2, EF16J2200A2 Heat Pump With Electric Heat, Limit Operation

Models: EF16J2200A2 EF20N2600A2 EF12F1900A2 EF08B1500A3

1 12
Download 12 pages 21.69 Kb
Page 9
Image 9
Heat Pump With Electric Heat

I Blower Coils

Mode

Constant Blower Fan Switch ON)

Thermostat calls for Heat

Sequence

Thermostat

to Con-

 

trol Board

24 volt

State

J

 

Control

 

 

 

 

Electric

G

 

On

 

 

Off

G&W1

&W2

On

 

 

Off

Installation Instructions

Of Operation

Control Function

Heat Only

Fan On.

Fan Off.

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.

2nd thenlst Stage Of Heat Off. 6 sec delay, then Fan Off.

Cooling Only Unit With Electric Heat

Constant Blower Fan Switch ON)

Cooling Only Unit (Thermostat calls for

Cooling)

Cooling Only Unit (Thermostat calls for Heat)

G

On

 

Off

Y&G

On

 

Off

G&W1 &W2

On

 

Off

Fan On.

Fan Off.

Compressor On, Fan On.

Compressor Off, 60 Second Delay - Then Fan Off.

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.

2rid thenlst Stage Of Heat Off. 6 sec delay, then Fan Off.

Heat Pump With Electric Heat

Heat Pump

Y&G&O

On

Compressor

On, Reversing

Valve

Energized,

Fan On.

(Thermostat

calls for

Off

Compressor

Off, 60 Second

Delay

And Then

Fan Off.

Cooling)

 

Heat Pump

Y & G

On

Compressor

On, Fan On

 

 

 

(Thermostat

calls for

 

 

 

 

 

 

Heat)

 

 

 

 

 

 

 

Heat Pump cannot

Y & G & Wl & W2

On

maintain proper temp.

 

 

Electric

Heat

Tempera-

 

Off

ture satifised

 

 

 

Heat Pump

 

Y&G&O&WI&W2

On

(Goes

into Defrost

 

 

Mode)

 

 

 

Off

 

 

 

 

Heat Pump

 

Y&G

Off

Room

temp.

satifised)

 

 

Heat Pump

 

G&W1 &W2

On

(Emergency

Heat)

 

Off

 

 

 

 

1st Stage Of Heat On, then 2nd Stage Of Heat On

2rid then 1st Stage Of Heat Off

Reversing valve switches unit to cooling, 1st Stage Of Heat On, then 2nd Stage Of Heat On

Reversing valve switches back to heating, 2rid then 1st Stage Of Heat Off

Compressor Off, 60 Second Delay And Then Fan Off.

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On. 2rid then 1st Stage Of Heat Off. 6 sec delay, then Fan Off.

NOTE: Electric Heat Elements are controlled by relays with a delay sequence from the logic board to provide sequencing between elements.

Limit Operation

The temperature limit responds to over-temperature conditions in the air duct. Ifthetemperaturelimittrips, theelectricheaterrelayswill

be de-energized and the fan relay will be energized. Once the limit resets, the control will resume normal operation. If the limit trips four times during a single call for heat, the control will go into a 1 hour soft lockout. During the soft lockout, the fan relay will respond to thermostat inputs but the heater relays are disabled. If the control detects a limit trip du ring the soft lockout, the control will go into a hard lockout. Once in a hard lockout, the fan relay is locked on and the heater relays are disabled. Turning the power to the unit off and then on will clear this state.

442 01 2204 01

9L_

Page 9
Image 9
Sears EF12F1900A2, EF20N2600A2, EF16J2200A2, EF08B1500A3 Heat Pump With Electric Heat, Limit Operation