Sears EF20N2600A2, EF12F1900A2, EF16J2200A2, EF08B1500A3 Condensate, Drain, Filter Installation

Models: EF16J2200A2 EF20N2600A2 EF12F1900A2 EF08B1500A3

1 12
Download 12 pages 21.69 Kb
Page 4
Image 4
Filter Installation

I Installation Instructions

Electric Furnace I

Figure 4 / Horizontal Drain Pan

1

 

 

Coil Support

Bracket

Horizontal

Drain Pan

(Right Hand Air_)

 

\

(Left Hand

Airflow)

 

 

il Support Bracket

Coil Support Bracket

Coil Access Panel

(Left Hand Airflow)

\

Drip Flanges

(Left Hand Airflow)

 

Horizontal Drain Pan

 

(Right Hand Airflow)

Drip Flanges

38-20-06

(Right Hand Airflow)

 

Filter Installation

Figure 5 Horizontal Installation

Filters must be field supplied. The blower cabinet is set up for an internal filter or a remote filter grille or other means may be pro- vided. Refer to ACCA Manual D for remote filter sizing.

To install an internal filter, remove screw securing filter door and slide filter into unit. Some filters are marked for airflow direction, make sure arrow points towards blower if marked. Washable fil- ters are offered as an accessory. Disposable filter sizes are listed in Filter Static Pressure Drop Table.

 

 

Condensate

Drain

 

 

 

The unit is provided with 3/4" National Pipe Thread (NPT) con-

 

 

densate drains. (Figure 1). Any drain can be used as a primary or

 

 

secondary drain. Condensate drain lines should be insta!led in a

 

 

manner that does not obstruct access to the filter.

 

 

There is a secondary drain fitting supplied with the unit that will

 

 

convert any of the primary condensate drain connections into a

 

 

secondary drain connection. This fitting should be insta!led in any

 

 

of the primary drain connections to convert it to a secondary drain.

 

 

1. Connect the drain lines to the appropriate drain fittings. 3/4"

 

 

PVC or other type of drain line may be used. The drain line

 

 

must not be smaller than the drain fitting.

Field-Fabricated

 

2. Insta!l a trap

in the drain line below

the bottom of the drain

Drain Pan

 

pan and pitch

the drain lines down

from the coil at least I/4"

Supports MUST run parallel with blower cabinet

=-_

per foot of run. Horizontal runs over 15 feet long must also

have an anti-siphon air vent (stand pipe), installed ahead

 

 

of the horizontal run. An extremely long horizontal run may require an oversized drain line to eliminate air trapping.