I Electric Furnace
3. Routetotheoutsideortoafloordrain,laundrytrayorwaste
line (sewer). Check local codes before connecting to a sewer line.
4.Insulate drain lines where sweating could cause water damage.
5.If a gravity drain cannot be used, install a condensate pump. Install the pump as close to the indoor section as possible.
SpecialNote For Downflow Installations
For downflow installations, a secondary overflow drain connection must be installed to prevent water from dripping onto live electrical components. Use the secondary fitting on the evaporator coil.
Waste Line Connection
If the condensate line is to be connected to a waste line, an open trap must be installed ahead of the waste line to prevent escape of
sewer gases. NEVER CONNECT THE DRAIN LINE DIRECTLY TO A WASTE LINE. ALWAYS INCLUDE AN AIR GAP AND
TRAP, (Figure 6). Be sure to keep the trap filled with water during the winter or off season.
| Installation Instructions |
Figure 6 | 1Condensate Drain to Waste Line |
T | Air Gap Above |
Condensate | uid Level |
| |
Line |
|
Sewer Line_q
Restrictor Orifice Selection
A restrictor orifice is located in a fitting at the distributor. The facto- ry installed restrictor orifice is identified on the unit rating plate.
The restrictor orifice may require changing to obtain best perfor- mance. Refer to the restrictor charts furnished with the outdoor unit.
Changing Restrictor Orifice
1.Remove the liquid line fitting and replace restrictor orifice.
(STANDARD RIGHT HAND THREAD)
2.Make sure the restrictor is installed with the rounded end to- ward the feeder tubes. See Figure 7.
Refrigerant Line Connections
Size refrigerant lines according to information provided with out- door condensing unit. Route the refrigerant lines to the coil in a manner that will not obstruct service access to the unit or removal
of the filter.
Remove rubber plugs from refrigerant connections using a pulling and twisting motion. Hold refrigerant lines to avoid bending or distorting.
2, Remove the coil door before brazing refrigerant connec- tions to prevent damage to paint finish.
3.Fit refrigerant lines into coil connections and remove the tubing plate and slide plate over the refrigerant lines to as- sure sufficient room for brazing.
Reinstall tubing plate and door and install the gasket, pro- vided with the unit, over the suction and liquid lines into the tubing plate recess to ensure an air seal around the coil.
See Figure 8.
Figure 7 J Restrictor Orifice
Nut and Liquid Line
_Rounded End
_ Feeder Tubes
Figure 8 J Refrigerant Lines
Gasket ,_
| j | Tubing Plate |
|
| Recessed |
Refrigerant k_ne_s__ | " | Area |
For Gasket |
Electric Heat
Refer to Electric Heat Installation Manual to install heaters.
442 01 2204 01 | 5L_ J |