Fume Hood Controller Owner's Manual
LAB00140R1
24V COMMON
24V HOT
GROUND
Figure 2. Power Wiring.
TEC0470R1
FLN TRUNK
+ - S
(SHIELD)(SHIELD)
(+)(+)
Figure 3. Communication Wiring.
Controller LED Indicators
The controller has six Light Emitting Diode (LED) indicators. See Table 2.
|
| Table 2. Controller LEDs. | |
LED Type | Label |
| Indication |
| (if present)* |
|
|
DO | LED 1 - LED 3 | Indicates the ON/OFF status of the DO associated with it. A | |
|
|
| glowing LED indicates that the DO is energized. |
|
|
|
|
Transmit | TX |
| Indicates, when flashing, that the controller is transmitting |
|
|
| information to the field panel. |
|
|
|
|
Receive | RX |
| Indicates, when flashing, that the controller is receiving |
|
|
| information from the field panel. |
BST | BST |
| Indicates, when flashing ON and OFF once per second, that |
”Basic Sanity Test” |
|
| the controller is functioning properly. |
|
|
|
|
Operator Display Panel (ODP)
The Operator Display Panel (ODP) is the interface device between the Fume Hood Controller and the operator. Its main functions are to display normal, warning, and alarm conditions to the operator. The ODP consists of a housing, three Light Emitting Diodes (LEDs), a liquid crystal display (LCD), four buttons, and a portable operator's terminal port. See Figure 4. The ODP buttons function as follows:
Horn Silence button – Pressing the Horn Silence button turns the audible alarm off for the current alarm event.
Emergency Purge button – Pressing the Emergency Purge button removes contaminated air from the fume hood by switching to an emergency exhaust flow level. The internal audible alarm will sound. Emergency Purge automatically overrides any other control mode in the Fume Hood Controller.
4 | Siemens Building Technologies, Inc. |