![](/images/new-backgrounds/1062747/6274753x1.webp)
Point Database
Address | Descriptor | Description |
|
|
|
56 | ODP STPT SW | Indicates if the lower left button on the ODP has been pressed. This is a toggle |
|
| action digital input; when pressed, the controller changes between HI and LOW |
|
| flow setpoints. |
|
|
|
57 | RIGHT SW | Indicates if the right auxiliary button on the ODP has been pressed. This is a |
|
| toggle action digital input; when pressed, the point is ON. If pressed again, the |
|
| point is OFF. |
|
|
|
63 | FLOW P GAIN | The proportional gain value for the fume hood flow control loop. |
|
|
|
64 | FLOW I GAIN | The integral gain value for the fume hood flow control loop. |
|
|
|
66 | FLOW D GAIN | The derivative gain value for the fume hood flow control loop. |
|
|
|
67 | FLOW BIAS | The bias, in percent, of the fume hood flow control loop. |
|
|
|
68 | CTRL LOOPOUT | Control output of the flow loop. Range: |
|
|
|
87 | FLOW HI STPT | The hi flow setpoint used in FLOW STPT. |
|
|
|
89 | HORN | When this point is set to DISABLE, the audible alarm will not sound. All other |
|
| alarm functionality is still operational. |
|
|
|
91 | BLANK DSPLY | When set to YES, the exhaust flow is not displayed at the ODP. |
|
|
|
92 | DO2 INVERTER | Setting to NCLOSE allows the controller to operate industry standard floating |
|
| control actuators. Setting this point may stop the failsafe operation from |
|
| functioning. |
|
|
|
93 | ENG UNITS | Toggles the display of the ODP from CFM to LPS. Toggling this point does not |
|
| change the displayed value at the portable operators terminal. |
|
|
|
94 | LAMP TEST | Turns on all lights, prompts, and the audible alarm at the ODP. |
|
|
|
96 | ALARM TIME | Time delay for the red and yellow alarm LEDs used to eliminate sudden changes |
|
| and false alarms. The exhaust flow must rise above any of the set limits (for |
|
| example, HI ALM LMT) for the amount of time specified at this point before the |
|
| ODP indicates an alarm condition. |
|
|
|
97 | DUCT AREA | Area of the duct, in square feet (SQM), where the air velocity sensor is located. |
|
|
|
98 | LOOP TIME | The time, in tenths of a second, between control loop calculations. |
|
|
|
99 | ERROR STATUS | The status code that indicates any errors detected during controller |
|
|
|
Siemens Building Technologies, Inc. | 19 |