Siemens SG-6048-01 manual Connecting Directly to a PC

Models: SG-6048-01

1 20
Download 20 pages 38.71 Kb
Page 8
Image 8

3 Installing the Converter

3.3Connecting Directly to a PC

To connect the Isolated Multi-Drop converter directly to a PC, you need an RS-232 serial cable of not more than 50 feet in length. Make sure the cable is a DCE-DTE cable, not a null modem cable. The following table lists the minimum set of required signals and the pin assignments for DB-25 to DB-25 and DB-9 to DB-25 cable connectors:

Table 3.1 RS-232 Pin Assignments

Pin Number

 

on Connector

Signal Name

 

 

2

TxD

 

 

3

RxD

 

 

4

RTS

 

 

7

GND

 

 

8

DCD

 

 

4.Insert the RS-485 connector(s) into the port(s) on the front of the converter. (Refer to section 3.1 for instructions on installing a connector on the RS-485 cable.)

5.Connect the supplied power cord to the 120 VAC connector on the converter, and plug the other end into any 120 VAC grounded power source.

6.Turn the converter’s power switch on, and verify that the PWR LED is lit. (Refer to Section 5 “Troubleshooting” if the PWR LED is not lit.)

7.Start your software.

To connect the converter to a PC, follow these steps while refering to Figure 3.3 below:

1.Connect the plug end of an RS-232 serial cable to the RS-232 port on the Isolated Multi-Drop converter.

2.Connect the socket end of the serial cable to an RS-232 port on your computer.

3.If you are using application software that requires direct DCD/RTS control, set the DCD/RTS switch to RTS and the MAN/AUTO switch to MAN. If you are using application software that does not require the direct DCD/RTS control, set the MAN/AUTO switch to AUTO, and use the BAUD thumbwheel to set the data rate to match that of the application software and the ACCESS devices on the network. (In automatic mode, the converter ignores the setting of the DCD/RTS switch.)

 

 

 

 

+

Device

 

 

 

22 AWG Shielded

-

#1

 

 

 

 

 

 

 

Twisted-Pair Cable

 

 

 

 

+

4000 Ft. Maximum

 

 

 

 

 

 

 

 

Port 4

SHLD

 

 

 

 

-

 

 

 

 

 

+

RS-485

 

 

 

 

Bus

 

 

 

Port 3

SHLD

+

Device

 

-

 

 

 

 

 

 

-

#n

 

 

+

 

Up to 32 devices

 

Port 2

SHLD

 

 

-

 

 

 

 

 

 

RS-232 Cable

 

 

 

 

 

50 Ft. Maximum

 

To Other

 

 

 

 

+

 

 

 

Port 1

SHLD

 

 

PC

RS-485

 

 

-

 

 

with

 

 

Devices

 

 

Supervisory

Isolated Multi-Drop

 

 

 

Software

 

 

 

 

Converter

 

 

 

 

Figure 3.2 Connecting the Converter Directly to a PC

Siemens Energy & Automation, Inc.

5

Page 8
Image 8
Siemens SG-6048-01 manual Connecting Directly to a PC