Technical data
General controller data | Mains voltage | AC 110...240 V +10 % / | ||
|
| Mains frequency | 48...63 Hz | |
|
| Safety class | II to DIN 0631 | |
|
| Mounting position | optional | |
|
| Terminals for | 2 x 1.5 mm² or 1 x 2.5 mm² | |
|
| Power consumption | max. 10 VA | |
|
| Safety extra | DC 24 V | |
|
| Contact rating of the control outputs |
| |
|
|
| (relays «K1...K3») | 2 A / AC 24...240 V |
|
| - Up to 2 x 105 switching cycles | ||
|
| - Up to 107 switching cycles | 0.1 A / AC 24...240 V | |
|
| Weight complete with housing | approx. 760 g | |
|
| Recommended actuator running time | 15...60 s | |
|
| Degree of protection of housing |
| |
|
| - | Front | IP 65, EN 60529 |
|
| - | Base | IP 20, EN 60529 |
Environmental |
|
| ||
Storage | DIN EN 60 | |||
conditions | Temperature range | |||
|
| Humidity | < 75 % r.h. | |
|
| Transport |
| |
|
| Temperature range | ||
|
| Humidity | < 75 % r.h. | |
|
| Operation |
| |
|
| Temperature range | ||
|
| Humidity | < 75 % r.h. |
Condensation, formation of ice and ingress of water are not permitted!
4/10
Building Technologies | CC1N7865en |