Function of the controller when used for burner control (cont´d)

Analog input 1 (actual value sensor)

Analog input 2 (external setpoint shift or external setpoint)

To acquire the actual value, a number of sensors can be connected to the RWF40...

 

 

 

 

Measurement range

 

 

 

 

 

 

 

2-or 3-wire resistance

Pt100 / IEC 751

-200...

+850 °C (-328...

+1562 °F)

sensors

Pt1000 / IEC 751

-200...

+850 °C (-328...

+1562 °F)

 

Ni100 / DIN 43760

-60...

+230 °C (-76...

+482 °F)

 

Ni1000 / DIN 43760

-60...

+230 °C (-76...

+482 °F)

 

LG-Ni1000

-50...

+160 °C (-58...

+320 °F)

 

 

 

 

 

 

Thermocouples

NiCr-Ni / type «K»

-200...

+1372 °C (-328...

+2502 °F)

 

Cu-Cu-Ni / type «T»

-200...

+400 °C (-328...+752 °F)

 

NiCroSil-NiSil / type «N»

-100...

+1300 °C (-148...

+2372 °F)

 

FeCuNi / type «J»

-200...

+1000 °C (-328...

+1832 °F)

 

Pt-RhPt / type «S»

0

...1768 °C (-32...

3214

°F) ¹)

 

Pt-RhPt / type «R»

0

...1768 °C (-32...

3214

°F) ¹)

 

Pt-RhPt / type «B»

0...

1820 °C (32...3308 °F) ¹)

Linearized standard

0

...20 mA

scalable -1999...

+9999

 

signals

4

...20 mA

scalable -1999...

+9999

 

 

DC 0

...10 V

scalable -1999...

+9999

 

 

DC 0

...1 V

scalable -1999...

+9999

 

¹) Only RWF40.0X2B97

The power provided for the measuring transducers is DC 24 V / 30 mA.

Feeding a signal to analog input 2, the controller´s setpoint can be influenced. The influence can be scaled.

The following signals can be used:

-Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA

-1 kpotentiometer in a 2-wire circuit

 

7/10

 

 

Building Technologies

CC1N7865en

HVAC Products

01.09.2005

Page 7
Image 7
Siemens siemens compact universal controllers manual Measurement range Or 3-wire resistance Pt100 / IEC