Alarm and fault messages
4.1 Fault handling
26

4 Alarm and fault messages

4.1 Fault handling

4.1.1 Fault types
There are two different types of fault, i.e. plant faults and operational faults. Plant faults are caused by
malfunctioning of an inverter component, while operational faults occur as a result of unexpected external
influences or logical conditions of the control software.
Examples of plant faults:
F48
F65
F97
Examples of operational faults:
F94
F96
It is however possible for an operational fault to be caused by a defective component.
Example: Fault 96 can be caused by a defective capacitor or transformer at the AC output.
4.1.2 Fault display / messages
Faults are displayed at the following locations:
Inverter control panel
Control panel in PPsolar
S7 software modules
WinCC
Fault messages are transferred to the following locations:
FAX Alarm
WEB’log
WinCC
Sequential faults: In some cases, the first fault can trigger further sequential faults which are
superimposed on the first fault or overwrite it on the display.