Dimensions and Weight
(if used)

connections and test again. If any connected phase LED still does not illuminate, contact Siemens Technical Support at: 1-888-333-3545.

11.The TPSA9040 is equipped with an audible alarm which will sound in the event of an alarm condition. This indicates a problem with the TVSS which requires further evaluation. There is no test or silence switch. De-energizing the TVSS will silence the alarm.

Figure 1

Typical TPSA9040 TVSS Installation

Dimensions and Weight

The TPSA9040 weight is 4 lbs.

2-5/32”

TPSA9040 TVSS

Mounting Screws

(4 places, not supplied)

Integral Chase Nipple (nut installed)

7-13/32”

0

0

 

20 Amp

 

2-Pole

 

Breaker

0

0

0

Electrical Panel

0

Chase Nipple Nut

Wiring to Breaker: Black

Black

Outer Breaker Panel Cover Screws

(6 places, typical)

Wiring to Neutral or Ground Bus: Ground - Green Neutral - White

3” 2-5/32”TPSA9040 TVSS7-13/32”Operation 1-1/2

1”

Operation

The Siemens Residential surge suppressor normally requires no remedial action. However in the event of a power anomaly or a malfunction, the operational status may change and may require action.

The table below outlines the operating conditions of the TPSA9040 and any correction action if required.

Figure 2

Typical Parallel Connections

To “Protected” Loads

Light

Light

Alarm

Audible

Corrective Action

1

2

Red

Alarm

 

 

 

 

 

 

Out

Out

Out

Off

Reset Breaker

If Breaker Trips Replace Unit

 

 

 

 

 

 

 

 

 

G

G

 

 

No Action

Phases

Neutral (if used)

Ground

Neutral Bus

Ground Bus

TVSS

Manual background Phase

Manual background Phase

Manual background Neutral

Manual backgroundManual background Ground

Interconnecting Wiring

Minimize Length

Avoid Sharp Bends

Out

G

Blinks

Sounds

Replace Unit

 

 

 

 

 

G

Out

Blinks

Sounds

Replace Unit

 

 

 

 

 

G

G

Blinks

Sounds

Check Neutral to Ground

Connection before Replacing Unit

 

 

 

 

This device features internal circuitry that will disconnect the surge protective component at the end of its useful life. Power will maintain to the load, however the load is now unprotected. Follow the manufacturer’s instructions for replacing the device.

NOTE: Safety Ground required for ALL units.