Specifications
Model | Voltage Rating and Service Type |
|
|
TPSA9040 | 120/240V Single Phase |
|
|
Item |
|
| Specification | |
|
|
|
| |
Temperature/Operating | F) to +60o C (+140o F) | |||
Temperature/Storage | ||||
|
|
|
| |
Audible Noise | None |
|
| |
|
|
| ||
Service Clearance | 36 inches (94.1 cm) in front of the unit | |||
|
|
| ||
Installation Type | Chase Nipple | |||
|
|
| ||
Wire Length vs. | 1 foot (31.7 cm) of wire = 1 nanosecond. | |||
Response Time and | 175 volts per foot (6kV/3kA, 8/20 micro- | |||
seconds) are added to the clamp voltage. | ||||
|
|
| ||
Wire Size | Wire Size = #12 AWG | |||
See Circuit Breaker for torque rating. | ||||
| ||||
|
|
| ||
Circuit Breaker and | 20 Amp | |||
Installation Torque | Torque to 18 inch lbs. | |||
|
|
| ||
| Per IEEE STD | |||
System Grounding | electronics/computer systems, the | |||
recommended ground impedance is 24 | ||||
| ||||
| ohms or less. | |||
|
|
|
| |
|
|
| ||
AC Surge Protection |
|
| ||
|
|
|
| |
Thermal Fusing |
|
| Yes | |
|
|
| ||
Catastrophic Surge Circuit |
| Yes | ||
|
|
| ||
Single Pulse Energy Dissipation |
| 1080 Joules | ||
|
|
|
| |
Spike Capacity |
|
| 40,000A | |
|
|
|
| |
Line Voltage |
|
| 120/240 1 Phase 50/60 Hz | |
|
|
|
| |
Initial Clamping Level |
|
| 400V | |
|
|
|
| |
Rated Voltage |
|
| 150V | |
|
|
|
| |
Response Time |
|
| <1 nanosecond | |
|
|
|
| |
Short Circuit Rating |
|
| 10,000A | |
|
|
|
|
Agency Approvals & Warranty
UL Listings | 1283 Filter, 1449 TVSS | |
|
| |
UL 1449 Rating | 400V | |
|
| |
Meets ANSI C62.41.1 | Yes | |
Requirements | ||
| ||
|
| |
Lightning Protection | Free replacement during | |
warranty period. | ||
| ||
|
| |
Product Warranty | 5 Years | |
|
| |
Appliance Warranty | 3 Years | |
|
|
Customer Service
TPS TECHNICAL SUPPORT AND CUSTOMER SERVICE
United States and Canada: |
This manual, and information about the entire Siemens product line are available on the Internet at: www.sea.siemens.com.
A Return Material Authorization number (RMA #) must be given by the Company prior to the return of any product. Returned products must be sent to the factory with the transportation charges prepaid.
Prior to calling Siemens for technical support, please have the following information available:
Model Number of unit: __________________________
Manufacture Date: | __________________________ |
Installation Date: | __________________________ |
Your Order Number: | __________________________ |
Return Shipment Address:
TPS Technical Support
14550 58th Street North
Clearwater, FL 33760
Attn: RMA#______________________
Page 4