Installation

Before you mount a flow switch, read "SAFETY" and "Installation" described in this chapter carefully to obtain safe and correct measurement.

Mounting

Use this flow switch under the specified operating pressure range.

Use this flow switch under the specified operating temperature range.

Withstand pressure is 2.25 MPa.

Do not install a flow switch at a foothold position.

Install a flow switch so that the flow direction agrees with the arrow direction on the side of the body.

Mount the body so that the bottom of the body does not face upward.

Provide a straight pipe length of more than eight times the pipe diameter to upstream and downstream of the flow switch.

Set Display Part proper position taking the cable entry and display position into account. Display Part rotates in 270 degree.

Piping connections

Observe the specified tightening torque when connecting pipes. Refer to the following table for the appropriate torque values.

Nominal size of screws

Appropriate tightening torque

(Nm)

 

 

 

Rc 1

36 to 38

 

 

Rc 11/2

48 to 50

 

 

Rc 2

48 to 50

 

 

When connecting pipeline to the switch, apply a spanner to the metal part of the piping section for the switch.

Make sure that sealing tapes will not enter inside the pipe when connecting pipes.

SWITCH FLOW

FLOW SWITCH

FLOW SWITCH

Spanner Spanner

FLOW SWITCH

6

7

Page 5
Image 5
Sierra Monitor Corporation PF2A7H instruction manual Installation, Mounting, Piping connections