7.2.2 Dehumidifying mode
1.The indoor fan is fixed in low speed
2. Low room temperature protection:
When room temperature decreases to below 10℃, indoor fan stop, when room temperature restores to over 12℃, indoor fan start.
3.At dehumidifying mode, the
7.2.3Heating mode
1. Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but
|
|
|
|
| Condition |
| Indoor fan speed | ||
|
|
|
|
| T= Indoor | exchanger |
|
|
|
|
|
|
|
| temp. |
|
|
|
|
| Indoor | exchanger | temp. | T<34℃ |
|
| Off | ||
| up |
|
|
| 34℃<T<37℃ |
|
| Breeze | |
|
|
|
|
| 37℃<T<44℃ |
|
| Low speed | |
|
|
|
|
| T> 44℃ |
|
| Setting fan speed | |
| Indoor | exchanger | temp. | T> 38℃ |
|
| Setting fan speed | ||
| down |
|
|
| 33℃<T<38℃ |
|
| Low speed | |
|
|
|
|
| 24℃<T<33℃ |
|
| Breeze | |
|
|
|
|
| T<24℃ |
|
| Off | |
1. Auto wind at heating mode |
|
|
|
|
| ||||
|
|
|
| Condition |
|
| Indoor fan speed |
| |
|
|
|
| T=Indoor |
|
| |||
| Room | temp. up |
| T<1.5℃ |
|
| High |
| |
|
|
|
| 1.5℃<T<2.5℃ |
|
| Mid. |
| |
|
|
|
| T>2.5℃ |
|
| Low |
| |
| Room | temp. down | T<1.0℃ |
|
| High |
| ||
|
|
|
| 1.0℃<T<2.0℃ |
|
| Mid. |
| |
|
|
|
| T>2.0℃ |
|
| Low |
|
2. Indoor evaporator
Condition | Compressor |
T= Indoor exchanger temp. |
|
T<48℃ | On |
53℃<T<63℃ | Decrease frequency of compressor |
T>63℃ | Off |
7.2.4Defrost operation
1. Defrosting condition:
The temperature of outdoor heat exchanger remains consecutively lower than
2. Ending condition of defrosting
15