7.2.2 Dehumidifying mode

1.The indoor fan is fixed in low speed

2. Low room temperature protection:

When room temperature decreases to below 10, indoor fan stop, when room temperature restores to over 12, indoor fan start.

3.At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode.

7.2.3Heating mode

1. Indoor Fan actions at heating mode

Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails.

Anti-cold wind control function at heating mode

 

 

 

 

 

Condition

 

Indoor fan speed

 

 

 

 

 

T= Indoor

exchanger

 

 

 

 

 

 

 

 

temp.

 

 

 

 

 

Indoor

exchanger

temp.

T<34

 

 

Off

 

up

 

 

 

34<T<37

 

 

Breeze

 

 

 

 

 

37<T<44

 

 

Low speed

 

 

 

 

 

T> 44

 

 

Setting fan speed

 

Indoor

exchanger

temp.

T> 38

 

 

Setting fan speed

 

down

 

 

 

33<T<38

 

 

Low speed

 

 

 

 

 

24<T<33

 

 

Breeze

 

 

 

 

 

T<24

 

 

Off

1. Auto wind at heating mode

 

 

 

 

 

 

 

 

 

Condition

 

 

Indoor fan speed

 

 

 

 

 

T=Indoor Temp.-Setting Temp.

 

 

 

Room

temp. up

 

T<1.5

 

 

High

 

 

 

 

 

1.5<T<2.5

 

 

Mid.

 

 

 

 

 

T>2.5

 

 

Low

 

 

Room

temp. down

T<1.0

 

 

High

 

 

 

 

 

1.0<T<2.0

 

 

Mid.

 

 

 

 

 

T>2.0

 

 

Low

 

2. Indoor evaporator high-temperature protection at heating mode

Condition

Compressor

T= Indoor exchanger temp.

 

T<48

On

53<T<63

Decrease frequency of compressor

T>63

Off

7.2.4Defrost operation

1. Defrosting condition:

The temperature of outdoor heat exchanger remains consecutively lower than -2°cfor more than 40 minutes,

2. Ending condition of defrosting