7.9 Outdoor unit LED display function:

1.When stand-by it display number of indoor unit online;

2.When operation it display frequency of outdoor unit;

3.When defrost it display “df”;

4.When a protection or error occurred, it display as the following table:

Display

Explanation

E0

EEPROM error

E1

No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective

E2

No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective

E3

No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective

E4

Outdoor temp. sensor or connector of temp. sensor is defective

E5

Compressor voltage protection

E6

No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective

E7

Indoor and outdoor communication error

P0

Compressor top protection against temperature

P1

High pressure protection

P2

Low pressure protection

P3

Compressor current protection

P4

Inverter module protection

P5

Outdoor low temp. protection

P6

Condenser high-temperature protection

7.10 Check function:

There is a check button on outdoor pcb. When push this button, the outdoor LED can display in sequence:

Capacity demand→Running mode →revised capacity → fan state →No.1 evaporator pipe temp. →No.2 evaporator pipe temp.→No.3 evaporator pipe temp.→No.4 evaporator pipe temp.→outdoor pipe temp. → Outdoor temp. →discharge gas temp.→current of outdoor unit → No. 1 opening degree of electronic expansion valve → No. 2 opening degree of EXV → No. 3 opening degree of EXV→No. 4 opening degree of EXV→indoor unit number→last protection/error code→capacity demand(cycle)

Explanation for the some display content:

1. Running mode:

Display

Corresponding mode

0Off

1Cooling mode

2Heating mode