7. Electric control functions:

7.1 Protection

1.3 minutes delay at restart for compressor.

2.Temperature protection of compressor top, compressor stops when the temp. of top of compressor is more than 120, compressor runs when the temp. of top of compressor is less than 105.

3.When AC voltage 270V for 30 seconds, Outdoor Unit stops operation and alarms. When AC voltage 260V for 30 seconds, Outdoor Unit resumes operation.

4.Inverter module protection, Inverter module Protection itself has a protection function against current, voltage and temperature.

5.Sensor protection at open circuit and breaking disconnection.

6.Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information and can’t return to normal operation automatically.

7.Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays failure information and can’t return to normal operation automatically.

8.Current protection: When the current is more than 25A, the compressor stops.

9.Outdoor condenser high temperature protection: Under cooling mode, if T3>65for 3 minutes, the compressor will stop. When T3<52, the protection is not valid.

10.Outdoor low temperature protection: If the outdoor temperature is lower than -15for

1hour, the compressor and fan motor will stop. If the outdoor temperature is higher than -12for 10 minutes and the compressor stops operation for 1h, or the outdoor temperature is higher than 5for 10 minutes, then restart and enter into the prior operation mode.

11.Compressor pre-heating function: When the outdoor temperature is lower than 3and the compressor stops operation for more than 3 hours, or the outdoor temperature is lower than 3and the power is just put on, the compressor enters into pre-heating condition. When outdoor temp. is more than 5or user operate it, pre-heating condition will finish.

7.2Operating mode

7.2.1Cooling mode

1.Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto: 2.Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.)

 

Condition

Indoor fan speed

 

 

 

Room temp. up

T<1.5

Low

 

 

 

 

1.5<T<4

Mid.

 

 

 

 

T>4

High

 

 

 

Room temp. down

T> 3

High

 

 

 

 

1<T<3

Mid.

 

 

 

 

T<1

Low

 

 

 

3.Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )

 

Evaporator Temp.

Compressor

 

 

 

 

T< 4

Off

 

T > 8

On