Slant/Fin XL-2000 dimensions Alternate Air Eliminating System

Models: XL-2000

1 15
Download 15 pages 59.15 Kb
Page 6
Image 6
Figure 6. Alternate Air Eliminating System

6

XL-2000

The opening size recommendation just given is for guidance only. It is the installer’s responsibility to provide air for combus- tion and ventilation to all appliances, under all operating con- ditions, for each installation. See NFPA 31, latest edition for more specific details.

INSTALLING CONTROLS AND ACCESSORIES ON BOILER UNITS

Notes:Jacket must be installed on boiler units prior to installa- tion of trim.

WATER BOILER TRIM, see page 2, figures 1 and 2 for tap- ping locations.

WATER PIPING FOR HOT WATER HEATING BOILERS NOTE: On knocked-down boiler only, jacket may be installed after supply piping connection, but must be installed prior to adding trim and piping returns and drain valve.

I.CIRCULATING SYSTEM

A.FORCED CIRCULATION hot water heating system: Use the top tapping as supply tapping, and use the front or rear bottom tappings for the return.

B.A FLOW CONTROL VALVE will prevent gravity circula- tion and is required when an external tankless heater, an indirect water heater or multiple circulators are

installed.

II.AIR CONTROL SYSTEMS

A.DIAPHRAGM-TYPE COMPRESSION TANKS are used to control system pressure in an AIR ELIMINATING SYSTEM: an automatic air vent is used to REMOVE air from the system water. (See figures 5 and 6)

If system pressure needs further control, add an addi- tional tank or install a larger capacity tank.

The automatic air vent should be installed in the top of

Figure 5. Air Eliminating System or Alternating Collecting System

the boiler, as in figures 5 and 6 and at radiation high points (see “C”).

B.CONVENTIONAL COMPRESSION TANKS (non- diaphragm type) are used to control system pressure in an AIR COLLECTING SYSTEM. Within the system, after initial start-up and venting, air is collected in the tank and acts in contact with the water to control pres- sure (see dashed area in figure 5 and paragraph “E”). Air is not vented from this system except at radiation high points (see “C”).

If system pressure needs further control, add another tank in parallel with the original tank or install a large capacity tank. Locate the tank at the inlet end of the pump near the boiler. (See figure 5)

C.HOT WATER RADIATION VENTING - Manual air vents should be installed at the top of all "drops" (where pip- ing goes downward). Air must be vented or purged from all zone lines to permit proper system heating.

D.PUMP LOCATION - Locating low-head pump(s) on return to boiler is only acceptable in residences of one or two stories. (See figure 6) The pump location shown in figure 5 is required in large, multi-story building instal- lations, especially when high-head pumps are used and is also recommended for all applications.

E.A conventional compression tank may be connected

directly to the 1/2" tapping on the boiler (see “Alternate Compression Tank”, figure 5).

IMPORTANT: Hot water heating systems containing high water volume, such as would occur with cast iron radiation, require special care with air elimination.

The circulator pump should be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction. (as shown in figures 5 and 6) For alternate circulator pump location on return for low-head pumps and one or two story buildings ONLY (see figure 6).

Figure 6. Alternate Air Eliminating System

Page 6
Image 6
Slant/Fin XL-2000 dimensions Alternate Air Eliminating System