PAGE 8
19A SERIES BOILER
INSTALLATION INSTRUCTIONS
13. CLEANOUT COVERS
Be sure the rope seals are in place around the groove in the cleanout cover plate. Install the plates on the boiler sections carefully to insure proper sealing all around, using the 5/16" x 2" special anchor bolt and 5/16" hex head nuts. After periodic flue cleaning, replace nuts at 10 lbs. torque. Use
14.REAR OBSERVATION PORTS
1.Locate steel “flapper door” (Item 6) as shown in FIGURE 9 below. Drive Item 7, “expansion pin”, into hole in Item 1 to secure 6 in position.
2.Lift Item 6 up and install Item 2, “hex bolt”.
3.Slide Item 3, “compression spring” over the hex bolt and screw Item 4 “hex nut” to hex bolt.
4.Screw Item 5, “ball knob” into position and lock location using Item 4 as a “jam” nut.
5.Adhere
7.
7 | 6 | |
5 | 1 | |
4 | ||
2 | ||
3 |
|
15. CONTROL LOCATIONS
NOTE
Jacket front panel should be in place before controls on front of front section are installed.
Refer to FIGURE 11 showing locations recommended for steam and water boiler limit and operating controls. Note the requirement for an operating temperature control whenever a tankless heater is called for. This is in addition to pressure limit controls and other operating controls on steam boilers.
NOTE
On steam boilers the 1" close nipple and 1" x 1/4" reducing coupling for operating control should be installed prior to jacket top panels.
16. JACKET
Jacket assembly details are contained in a separate instruction booklet.
17. SAFETY AND RELIEF VALVES
Safety and relief valves sized on the output rating of each boiler size are furnished along with the necessary pipe and fittings for installation in the back section. The valve discharge connections should be piped to a location where people will not be exposed to hot vapor or liquid. Any discharge piping should be supported so as to prevent exerting any strain on the valve body by the weight of the piping. See FIGURE 10.
FOR DISCHARGE PIPING THROUGH ROOF CONSULT THE SMITH COMPANY
INSULATING TAPE
FIGURE 9
IMPORTANT
Item 6 must always be part of the assembly. Check condition twice a year and replace as needed.
RELIEF OR SAFETY VALVE DO NOT REMOVE RATING OR WARNING TAGS.
SUPPORT DISCHARGE PIPING SO AS TO AVOID STRAIN ON VALVE BODY
DISCHARGE PIPE SIZE
TO EQUAL VALVE OUTLET. DO NOT RESTRICT FLOW.
DISCHARGE SO AS TO AVOID EXPOSURE OF PERSONS TO HOT LIQUID OR VAPOR. LEAVE OPEN END VISIBLE FOR PERIODIC INSPECTION FOR SLOW LEAKAGE OR DRIPS.
FIGURE 10
Some state and local codes require steam safety valves be piped to the atmosphere outside the building.