SECTION 2: BOILER INSTALLATION
STEP 1: LOCATING/SETTING BOILER
Boiler may be installed in an alcove (see dimensions in Figure 2.1). Locate boiler so connecting flue pipe between draft hood and chimney is as short as possible.
Observe the following minimum clearances to combustibles: 18" on sides...alcove at front...28" at top...18" at rear...6" from flue pipe in any direction. Maintain a minimum 1” clearance between hot water piping and combustible materials. Local code requirements may specify greater clearances and must be adhered to.
Remove boiler from carton and set it in position. Install on
FIGURE 2.1: MODEL GB200 BOILER DIMENSIONS
Remove all packing material from boiler. Check that burners, draft diverter and controls are in proper position.
Boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (low water
NOTE: Do not loosen tie rods on boiler absorption unit. They are intended to accommodate thermal expansion. Loss of boiler's structural integrity and water leaks/dam- age may result.
WARNING: Never install boiler on carpeting as heat damage and/or fire may result.
|
| BOILER |
| DIMENSIONS | MINIMUM CLEARANCES |
| ||
|
|
|
|
|
| |||
|
|
|
|
| TO COMBUSTIBLES |
| ||
|
| MODEL |
| A | B |
| ||
|
| 15 3/8" | 5" | Top: | 28" |
| ||
|
| Rear: | 18" |
| ||||
|
| 18 7/8" | 6" |
| ||||
|
| Left & Right: 18" |
| |||||
|
| 18 7/8" | 6" |
| ||||
|
| Front: | ALCOVE |
| ||||
|
| 22 3/8" | 7" |
| ||||
|
|
|
|
| ||||
|
|
| PRESS. |
|
|
|
| |
| B |
| RELIEF VALVE |
|
|
|
| |
|
|
|
|
|
|
|
| |
|
| PRESSURE CONTROL |
|
|
|
|
| |
PRESS. | SPILL SWITCH | 3" |
|
|
|
|
|
|
GAUGE |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
| 2" STEAM |
|
|
| 3/4" PLUGGED |
| |
| 9 7/8" | SUPPLY |
|
|
|
|
| |
LOW |
|
|
|
|
| TAPPING |
| |
|
|
|
|
|
|
|
| |
WATER |
| WATER |
|
|
|
|
|
|
| LEVEL |
|
|
|
|
|
| |
|
| INDICATOR |
|
|
| WATER |
|
|
|
|
|
|
|
|
|
| |
41" |
|
|
|
|
| LINE |
|
|
2 1/2" |
| 1/2" |
|
|
|
|
| 2" RETURN |
|
|
|
|
|
|
| ||
|
| PLUGGED | GAS |
| ROLLOUT SWITCH | 26 7/8" | REAR | |
|
| TAPPING |
|
| ||||
|
| VALVE |
|
|
| 23 7/8" | ||
|
|
|
|
|
| 23 1/4" | ||
|
| 23 1/4" |
|
|
| |||
21" |
|
|
|
|
| |||
20" |
|
|
|
|
| |||
|
|
|
|
| 18 1/4" |
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
14 3/4" |
|
|
|
|
|
|
| 14 3/4" |
|
| 3 3/8" |
|
|
|
|
|
|
2" RETURN | 16 1/2" |
|
|
|
|
|
| 2 1/2" |
18 1/8" |
|
|
|
|
|
| ||
FRONT |
|
|
|
|
|
| 18 1/8" | |
21 7/8" | 2 3/8" 6 3/4" |
|
| A |
| |||
|
|
|
| |||||
|
|
|
|
| ||||
| PROBE LOCATION FOR ELECTRIC LWCO. |
|
|
|
| |||
| NOTE: OPTIONAL FLOAT LOW WATER |
|
|
|
4