FIGURE 2.7: GAS PIPE SIZING TABLES & EXAMPLE
Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of
0.5Psig or Less and a Pressure Drop of 0.3 Inch Water Column (Based on a 0.60 Specific Gravity Gas)
| Nominal |
|
|
|
|
|
|
| Length of Pipe, Feet |
|
|
|
|
|
|
| ||
Iron Pipe | Internal |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Size, | Diameter, | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 125 | 150 | 175 | 200 | ||
| Inches | Inches | ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
1/4" | .326 | 32 | 22 | 18 | 15 | 14 | 12 | 11 | 11 | 10 | 9 | 8 | 8 | 7 | 6 | |||
3/8" | .493 | 72 | 49 | 40 | 34 | 30 | 27 | 25 | 23 | 22 | 21 | 18 | 17 | 15 | 14 | |||
1/2" | .622 | 132 | 92 | 73 | 63 | 56 | 50 | 46 | 43 | 40 | 38 | 34 | 31 | 28 | 26 | |||
3/4" | .824 | 278 | 190 | 152 | 130 | 115 | 105 | 96 | 90 | 84 | 79 | 72 | 64 | 59 | 55 | |||
1" | 1.049 | 520 | 350 | 285 | 245 | 215 | 195 | 180 | 170 | 160 | 150 | 130 | 120 | 110 | 100 | |||
1.380 | 1,050 | 730 | 590 | 500 | 440 | 400 | 370 | 350 | 320 | 305 | 275 | 250 | 225 | 210 | ||||
1.610 | 1,600 | 1,100 | 890 | 760 | 670 | 600 | 560 | 530 | 490 | 460 | 410 | 380 | 350 | 320 | ||||
2" | 2.067 | 3,050 | 2,100 | 1,650 | 1,450 | 1,270 | 1,150 | 1,500 | 990 | 930 | 870 | 780 | 710 | 650 | 610 | |||
2.469 | 4,800 | 3,300 2,700 | 2,300 | 2,000 | 1,850 | 1,700 | 1,600 | 1,500 | 1,400 | 1,250 | 1,130 | 1,050 | 980 | |||||
3" | 3.026 | 8,500 | 5,900 | 4,700 | 4,100 | 3,600 | 3,250 | 3,000 | 2,800 | 2,600 | 2,500 | 2,200 | 2,000 | 1,850 | 1,700 | |||
| 4" | 4.026 | 17,500 | 12,000 | 9,700 | 8,300 | 7,400 | 6,800 | 6,200 | 5,800 | 5,400 | 5,100 | 4,500 | 4,100 | 3,800 | 3,500 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied
Petroleum Gases (at 11 Inches Water Column Inlet Pressure)
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal |
|
|
|
|
| Length of Pipe, Feet |
|
|
|
| |||
Iron Pipe |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||
Size, |
|
|
|
|
|
|
|
|
|
|
|
| |
10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 125 | 150 | ||
Inches | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
1/2" | 275 | 189 | 152 | 129 | 114 | 103 | 96 | 89 | 83 | 78 | 69 | 63 | |
3/4" | 567 | 393 | 315 | 267 | 237 | 217 | 196 | 185 | 173 | 162 | 146 | 132 | |
1" | 1071 | 732 | 590 | 504 | 448 | 409 | 378 | 346 | 322 | 307 | 275 | 252 | |
2205 | 1496 | 1212 | 1039 | 937 | 834 | 771 | 724 | 677 | 630 | 567 | 511 | ||
3307 | 2299 | 1858 | 1559 | 1417 | 1275 | 1180 | 1086 | 1023 | 967 | 866 | 787 | ||
2" | 6221 | 4331 | 3465 | 2992 | 2646 | 2394 | 2205 | 2047 | 1921 | 1811 | 1606 | 1498 |
Example: Boiler Model
135,000 Btu per hour = 135 cu.ft. per hour
1000 Btu per cu.ft.
1.Find 30 ft. in upper portion of the table for natural gas under "Length of Pipe, Feet" heading.
2.Moving down the column, match required capacity. Higher capacity is acceptable. In our case it is 152 cu.ft.
3.Move to
Testing Gas Piping
DANGER: Before placing gas piping into service, carefully test it to assure every joint is gas tight. Bubble test all joints with a soap solution. NEVER TEST WITH AN OPEN FLAME AS FIRE OR EXPLOSION WILL RESULT.
For any pressure testing in excess of 1/2 psi, the boiler and its individual shutoff valve must be isolated from the piping system by disconnecting them and capping the outlet(s). For any pressure testing equal to or less than 1/2 psi, the boiler must be isolated from the piping system by closing its manual shutoff valve.
Minimum pressure required at the gas valve inlet is 5" W.C. for natural gas and 11" W.C. for propane. Maximum pressure allowable at the gas valve inlet is 12" W.C. If the gas pressure is above these limits, a pressure regulator must be installed. If the gas pressure is below these limits, contact the local utility.
8