Tower Framework

Maintenance

sibility to institute a program of water treatment and maintenance that will minimize their impact. (See Water Treatment on pages 18 and 19.)

Tower Framework

Inspect for cracks and spalling and repair if necessary. Keep bolts tight in the mechanical equipment supports. Maintain a positive Langelier index in your circulating water. (See Water Treatment on pages 18 and 19.)

Drive Shaft

Check drive shaft alignment and condition of couplings every six months. See the Drive Shaft Service Manual for correcting misalignment, balanc- ing, or replacing parts.

Electric Motor

Lubricate and maintain each electric motor in accordance with the man- ufacturer’s instructions. If repair work is necessary, contact the nearest representative of the motor manufacturer. See Warranty Section of Marley Service Manual on Electric Motors.

Fan

Inspect fan blade surfaces every six months. For detailed maintenance information, refer to Marley Fan Service Manual.

Geareducer

Make weekly and monthly oil checks. Inspect internal parts during sea- sonal oil change. Refer to the Geareducer Service Manual for detailed maintenance instructions.

Cold Water Collection Basin

Inspect collection basin occasionally for cracks, leaks, and spalling and repair if necessary. Maintain a positive Langelier index in your circulating water. (See Water Treatment on pages 18 and 19.) Keep cold water out- lets clean and free of debris. Make-up and circulating water controls must operate freely and maintain the desired water quantity in the system.