Maintenance
Well maintained equipment gives the best operating results and the least maintenance cost. A regular inspection schedule is recommended to insure effective safe operation of the cooling tower. Use the Inspection and Maintenance Schedule on page 25 to obtain continuously good performance with least tower maintenance. See the Inspection Checklist on pages 26 and 27 in this manual. Keep a continuous lubrication and maintenance record for each cooling tower. Conduct regular inspections, repair personnel safety items (items 20 and 21 in the table on page 25) and maintain records of
Hot Water Distribution System
Keep the circulating water and distribution system (piping and nozzles) clean and free of dirt, algae, and scale. Algae and scale may clog nozzles, eliminators, fill, and piping, and may collect on the equipment served thus reducing its performance
See Caution note below under Fill.
Access
The optional access door in the fan deck with an optional short ladder to the top of the fill provides a means for inspection of the plenum area above and below the eliminators.
Removal of eliminator packs allows access to the spray chamber for inspection and maintenance of the nozzles and top of fill. Under no circumstances are the eliminators to be used as a walking surface. Provide top surface protection before walking on the fill.
Fill
Clean,
Contributors to the clogging of fill are trash and debris, algae, slime, and
➠
15