Maintenance

Note

Caution

Caution

Maintenance

Well maintained equipment gives the best operating results and the least maintenance cost. A regular inspection schedule is recommended to insure effective safe operation of the cooling tower. Use the Inspection and Maintenance Schedule on page 25 to obtain continuously good performance with least tower maintenance. See the Inspection Checklist on pages 26 and 27 in this manual. Keep a continuous lubrication and maintenance record for each cooling tower. Conduct regular inspections, repair personnel safety items (items 20 and 21 in the table on page 25) and maintain records of all—this is especially important. For a supply of check list forms, contact your Marley sales office or representative.

Hot Water Distribution System

Keep the circulating water and distribution system (piping and nozzles) clean and free of dirt, algae, and scale. Algae and scale may clog nozzles, eliminators, fill, and piping, and may collect on the equipment served thus reducing its performance

See Caution note below under Fill.

Access

The optional access door in the fan deck with an optional short ladder to the top of the fill provides a means for inspection of the plenum area above and below the eliminators.

Removal of eliminator packs allows access to the spray chamber for inspection and maintenance of the nozzles and top of fill. Under no circumstances are the eliminators to be used as a walking surface. Provide top surface protection before walking on the fill.

Fill

Clean, free-flowing, unobstructed fill is key to the continued efficient operation and performance of a cooling tower. The owner/operator must keep the circulating water clean by treatment, screening, or filtering to avoid the possibility of fill clogging. Sea water, if used, will typically present increased clogging problems due to suspended solids and/or biological growth if the water is not properly filtered and treated. The dissolved ions do not present unusual clogging problems.

Contributors to the clogging of fill are trash and debris, algae, slime, and scale—with the effects of scale often being worsened by the presence of suspended muds. All of these can be controlled with some combination of water treatment, screening, and filtration, and it is the owner’s respon-

15