Seasonal Shutdown Instructions
Tower
Drain all tower piping.
During shutdown, clean the tower and make any necessary repairs. Ap- ply protective coating as required to all metal parts. Particular attention should be given to mechanical equipment supports, drive shaft and drive shaft guards, Geareducers, and motors.
See Warning note on page 17 regarding tower cleaning.
Visually inspect for concrete deterioration. If ambient temperature is 32°F (0°C) or below, do not put cold water on tower.
Mechanical Equipment
Shutdown for less than 3 months.
Each month, drain water condensate from the lowest point of the Geareduc- er and its oil system. Check oil level and add oil if necessary. Operate Geareducer briefly to recoat all interior surfaces with oil. At
Refer to Geareducer Service Manual for maintenance and lubrication instructions.
Shutdown for 3 months or longer.
If the motors have space heaters, operate mechanical equipment one hour each month. Space heaters should be energized anytime motor is not operating. If the motors do not have space heaters, operate mechanical equipment one hour each week. At
Refer to Geareducer Manual for instruction on changing oil. Refer to Marley Downtime Instruction Manual for downtime of 6 months or longer.
Electric Motors
▲Caution
Do not start motor without determining that there will be no interfer- ence with free rotation of the fan drive. Refer to Marley Electric Motor Service Manual.
If shutdown period is longer than seasonal, contact your Marley sales office or representative for additional information.
20