![Miscellaneous Options](/images/new-backgrounds/34865/3486535x1.webp)
Marley / NC Class Stainless CoolingTower / Specifications: Options | 18 |
|
Specifications |
| Specification Value |
shall be operated as a stand- alone sys- tem without the need for a BMS system. Operator controls shall be mounted
on the front of the enclosure and shall consist of start and stop control, bypass/ VFD selector switch, Auto/Manual selector switch, manual speed control, and
in
Miscellaneous Options
Motor out of the Airstream:
6.1Add the following to the end of this paragraph: The motor shall be mount- ed outside the casing of the tower, and shall be connected to the gear reducer by a
Fan Cylinder Extensions:
9.1Insert the following after the first sentence: Fan cylinder extensions shall be provided to elevate the fan dis- charge to a height of ___ m above the fan deck level.
■For many years, a feature of Marley cooling towers was that the electric motors were located outside the fan cylinders, where they were easily accessible, and where they were not subjected to the constant humidity that exists inside the tower plenum.
Although improved motor designs (insulation, bearings, seals, and lubricants) have now made it fea-
sible for us to locate the motor inside the tower in
■Extensions are available in 305mm increments to a maximum height equal to the diameter of the fan. Such extensions may be considered necessary in order to elevate the discharge beyond the bounds of an enclosure. Discuss applicability with your local Marley sales representa- tive.