SPX Cooling Technologies SS-NC-08A Specifications, Specification Value, Basin Sweeper Piping

Models: SS-NC-08A

1 24
Download 24 pages 25.15 Kb
Page 22
Image 22
Multicell Basin Equalizer Outlets:

Marley / NC Class Stainless CoolingTower / Specifications: Options

22

 

Specifications

 

Specification Value

______ psf, as well as a ______ seismic

load. The fan deck and hot water basin covers shall be designed for 50 psf live load or a 200 lb. concentrated load.

Guardrails, where specified, shall be capable of withstanding a 200 lb. con- centrated live load in any direction, and shall be designed in accordance with OSHA guidelines.

Multicell Basin Equalizer Outlets:

11.1Add the following paragraph in the Access section: A hole and bolt circle shall be provided in the depressed sec- tion of the basin for equalizer piping between cells. A full-face, .25" thick, 50 durometer gasket shall be provided at each equalizer location.

Basin Sweeper Piping:

11.1Add the following paragraph in the Access section: The cold water basin shall be equipped with PVC sweeper piping with plastic eductor nozzles.

The piping should create a grid under the fill and force all dirt and debris to the depressed section of the collection basin.

Extended Geareducer Lube Line with Dipstick:

6.1Add the following paragraph in the Mechanical Equipment section: An external oil level dipstick shall be locat- ed adjacent to the motor at the fan deck surface and shall be accessible from a portable maintenance ladder.

Used as water level equalizers between multicell towers. Not intended for water migration. Piping and attachment hardware by others. Flat faced flange required.

PVC sweeper piping and Lakos nozzles. Designed for the following flows at 20 psig:

NC8301 thru NC8304, 33m3/h NC8305, 47m3/h

NC8306 thru NC8312, 64m3/h

The dipstick option is accessible from a portable maintenance ladder on one and two cell towers only. Maintenance considerations recom- mends this option be combined with the ladder and guardrail option on installations of three or more cells since the dipstick cannot be reached without accessing the fan deck.

Page 22
Image 22
SPX Cooling Technologies SS-NC-08A specifications Specifications, Specification Value, Multicell Basin Equalizer Outlets