Marley / NC Class Stainless CoolingTower / Specifications: Base | 4 |
|
Specifications |
| Specification Value |
1.0Base:
1.1 | Provide an induced draft, crossflow | ■ Your specification base establishes the type, configuration, base materi- |
| type, factory assembled, film fill, | al and physical limitations of the cooling tower to be quoted. During the |
| industrial duty, stainless steel cooling | planning and layout stages of your project, you will have focused your |
| tower situated as shown on the plans. | attention on a cooling tower selection that fits your space allotment, |
| The limiting overall dimensions of | and whose power usage is acceptable. Limitations on physical size and |
| the tower shall be _____ wide, _____ | total operating horsepower avoid the introduction of unforeseen opera- |
| long, and _____ high. Total operating | tional and |
| kilowatt of all fans shall not exceed | the maximum fan kW/cell will work to your advantage. |
| ____ kW, consisting of ___ @ _____ | The benefit of crossflow towers is that they are inherently easy to oper- |
| kW motor(s). Tower shall be similar and | |
| equal in all respects to Marley Model | ate, access and maintain. Compared to counterflow towers, crossflow |
| ____________. | towers have a spacious plenum between banks of fill for easy access to |
|
| all of the tower’s internal components, plus the water distribution sys- |
|
| tem is adjacent to the fan deck and can be maintained during operation. |
|
| The NC is also available unassembled for |