ELECTRICAL HAZARDS

Table 1. Minimum approach distances from energized conductors for qualified line-clearance arborists and qualified line-clearance arborist trainees.

 

Includes 1910.269

Includes 1910.269

Includes 1910.269

Nominal

elevation factor, sea

elevation factor,

elevation factor,

Voltage

level to 5000 ft1)

5001–10,000 ft1)

10,000–14,000 ft1)

kV phase-to-phase

ft-in

m

ft-in

m

ft-in

m

0.05–1.0

Avoid contact

Avoid contact

Avoid contact

1.1–15.0

2-04

0.71

2-08

0.81

2-10

0.86

15.1–36.0

2-09

0.84

3-02

0.97

3-05

1.04

36.1–46.0

3-00

0.92

3-05

1.04

3-09

1.14

46.1–72.5

3-09

1.14

4-03

1.30

4-07

1.40

72.6–121.0

4-06

1.37

5-02

1.58

5-07

1.70

138.0–145.0

5-02

1.58

5-11

1.80

6-05

1.96

161.0–169.0

6-00

1.83

6-10

2.08

7-05

2.26

230.0–242.0

7-11

2.41

9-00

2.75

9-09

2.97

345.0–362.0

13-02

4.02

15-00

4.58

16-03

4.96

500.0–550.0

19-00

5.80

21-09

6.63

23-06

7.17

765.0–800.0

27-04

8.34

31-03

9.53

33-10

10.32

1) Exceeds phase-to-ground; elevation factor per 29 CFR 1910.269.

Table 2. Minimum approach distances to energized conductors for persons other than qualified line-clear- ance arborists and qualified line-clearance arborist trainees.

Nominal Voltage

 

Distance

kV phase-to-phase1)

 

 

 

ft-in

m

0.0–1.0

10-00

3.05

1.1–15.0

10-00

3.05

15.1–36.0

10-00

3.05

36.1–50.0

10-00

3.05

50.1–72.5

10-09

3.28

72.6–121.0

12-04

3.76

138.0–145.0

13-02

4.00

161.0–169.0

14-00

4.24

230.0–242.0

16-05

4.97

345.0–362.0

20-05

6.17

500.0–550.0

26-08

8.05

785.0–800.0

35-00

10.55

1) Exceeds phase-to-ground.