Additive Feeders Chapter 4: Operation 31 of 55
Resetting the Unit to Un-Programmed State
The factory-default settings can be easily restored using either of two methods. Both
methods require the Program Enable jumper to be in the “On” position. The first is to apply
power to the unit with both the Enter and Down buttons pressed for 3 seconds. The second is
to change the value of parameter 95 to 5.
JP1 (Program Enable Jumper)
The JP1 jumper is located under the dust cover on the back end of the upper board. When the
jumper is set to the "Off" position, all programming features are locked out to the front panel
user. When the jumper is in the "On" position, the programming parameters are open to
change. JP1 is shipped in the "Off" position.
Programming Step by Step Guide
1. Remove the power source from the controller. Following the procedures in your
facility, lockout or tagout the power source.
2. Remove the cover from the control enclosure.
3. At the connection end of the drive, lift the black plastic dust cover up slightly and
slide it out of the back of the drive.
4. Locate the jumper labeled “JP1.”
5. Move the JP1 jumper from the “OFF” position to the “ON” position.
6. Slide the black plastic cover back into position.
7. Install the enclosure cover.
8. Remove any lockout/tagout devices in use as per procedures in place at your
facility, then connect the controller to the power source and power the unit up.
9. Press the Enter button until parameter selection mode is entered. When the drive is
in Parameter-Selection Mode, the far left of the display will be a “P.”
10. Use the Up and Down Arrow buttons to navigate to the desired parameter.
11. When the parameter number to be changed is displayed press the Enter button to
enter Value Mode. When in Value Mode, the two dots which form the colon
between digits two and three will alternately flash.
12. Use the Up and Down Arrow buttons to change the parameter’s displayed value.
13. Press the Enter button to return to Parameter-Selection Mode.