Resetting the Unit to Un-Programmed State
The
JP1 (Program Enable Jumper)
The JP1 jumper is located under the dust cover on the back end of the upper board. When the jumper is set to the "Off" position, all programming features are locked out to the front panel user. When the jumper is in the "On" position, the programming parameters are open to change. JP1 is shipped in the "Off" position.
Programming Step by Step Guide
1.Remove the power source from the controller. Following the procedures in your facility, lockout or tagout the power source.
2.Remove the cover from the control enclosure.
3.At the connection end of the drive, lift the black plastic dust cover up slightly and slide it out of the back of the drive.
4.Locate the jumper labeled “JP1.”
5.Move the JP1 jumper from the “OFF” position to the “ON” position.
6.Slide the black plastic cover back into position.
7.Install the enclosure cover.
8.Remove any lockout/tagout devices in use as per procedures in place at your facility, then connect the controller to the power source and power the unit up.
9.Press the Enter button until parameter selection mode is entered. When the drive is in
10.Use the Up and Down Arrow buttons to navigate to the desired parameter.
11.When the parameter number to be changed is displayed press the Enter button to enter Value Mode. When in Value Mode, the two dots which form the colon between digits two and three will alternately flash.
12.Use the Up and Down Arrow buttons to change the parameter’s displayed value.
13.Press the Enter button to return to