Sterling GP Series specifications Operator Setpoints Screen

Models: GP Series

1 44
Download 44 pages 61.28 Kb
Page 24
Image 24
Figure 6 - Operator Setpoints Screen

Enter the established Operator Password by depressing the Manual background to move the

position of the cursor, and then depressing the Manual background or Manual background button to increment or decrement the number. Once all of the numbers have been

entered depress the Manual background to accept the password. The following screen will appear.

Figure 6 - Operator Setpoints Screen

5.Depress Manual background to move the cursor to the Leaving Temp line. Use the Manual background or Manual background button to increment or decrement the value. Depress Manual background to accept the value and move the cursor down one line.

6.Depress the Manual background button twice to return to the main status screen.

7.Depress the Manual background to start the chiller.

8.Check pump rotation

9.Check the pump amp draw and pump pressure. Make sure that the amp draw reading is within the running load and service factor amps.

10.Operate the chiller, looking for any leaks and listening for unusual noises or vibrations that could indicate improper operation.

GP Series Portable Chillers

Chapter 4: Operation

24 of 44

Page 24
Image 24
Sterling GP Series specifications Operator Setpoints Screen