A-2 9710 System Assurance Guide MR0012J
Table A-3. Optional Power Distribution Unit (PDU) Specifications
Power cable U.S./Canada:
120 VAC UL/CSA power cable
International:
200–240 VAC HAR power cable
Input voltage range
Nominal voltage
100–254 VAC
120 or 240 VAC
Power configuration U.S./Canada:
Single phase 120 VAC, 47–63 Hz, 6 A Service, 3-wire
International:
Single phase 200–240 VAC, 47–63 Hz, 3 A Service, 3-
wire
Power consumption 38 W
Maximum heat
output
128 Btu/hr
Table A-4. LSM Environmental Specifications
Tempera ture
Operating
Storage
Shipping
15° to 32°C (59° to 90°F)
10° to 40°C (50° to 104°F)
10° to 40°C (50° to 104°F)
Relative Humidity
Operating
Storage
Shipping
20% to 80% (noncondensing)
10% to 95% (noncondensing)
10% to 95% (noncondensing)
Wet Bulb Maximum
Operating
Storage
Shipping
29.2°C (84.5°F)
35°C (95°F)
35°C (95°F)
Altitude
Operating
Storage
Shipping
0 to 3.05 km (0 to 10,000 ft)
0 to 3.05 km (0 to 10,000 ft)
0 to 15.24 km (0 to 50,000 ft)