STUDER INNOTEC |
Equalization mode should never be used when using
4.7.4 Charging current
The maximum charging current for the battery can be adjusted with the Turning Knob 22 (CHARGER). The charging current of the battery should be set to approximately 10 – 20% of the battery capacity (at C10). This means that the charging current for a battery with 300Ah should be set between 30 – 60A.
The charging current is displayed on POWER MONITOR (25) of the front panel or on the Remote Control.
4.7.5 Battery Condition
Notice: the exact measure of the battery state of charge with electrical parameters is
−Battery charge or discharge with too high currents
−Battery cable cross section too small
−Battery connections badly tightened or corroded
−Charge of the battery with external battery charger
−Discharge of the battery with users not connected to the
−Work with defective or sulphated batteries
This means that the display can, within few minutes during the charge, commute from 25% to 75% or during the discharge, to the opposite direction.
As many of the working cases mentioned above often occur, the measure system of the
For safety reasons, you must get the recommended charge voltage and charge currents from your battery supplier. The voltage levels and charge characteristics can be changed through Programming. The instruction for programming of battery charger is in the section „Programming“ (Chap. 5.3). The correct charging is mandatory for a safe function and a
The battery charger functions are described by the graphic in chap. 4.7.1.
4.8The Transfer system
When an AC voltage is at the input AC IN of the
| 18/77 |