5 Programming (possible only with the remote control RCC-01)

The XP-COMPACT (except for 60Hz versions) is equipped with a Flash processor fitted out with EEPROM Memory, which means that even when it is disconnected from the battery, the parameters that were programmed for the application remain after a new connection to the battery.

It is possible to reinitialize (RESET) the XP-COMPACT by pressing simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A beep will confirm the RESET. The inverter switches off after this operation. It can be turned on again after the beep. The programmed parameters will remain.

5.1Standard setting

The XP-COMPACT is delivered with the following default settings:

Auxiliary contact: active in case of defect or manual turn off with the LED 10/11/12/13

Battery voltage :

Low voltage

11.6V / 23.2V / 46.4V

 

Float Charge

13.5V / 27.0V / 54.0V

 

End of Charge Voltage

14.4V / 28.8V / 57.6V

 

Equalization

15.6V / 31.2V / 62.4V

Absorption Time :

 

2 Hours

Equalizing Time :

 

20 Minutes

5.2Reset value (default settings)

To come back to the default settings, press simultaneously on the push buttons 20/21 during at least 2 seconds. A beep will confirm the comeback to the factory settings. The inverter switches off after this operation. It can be turned on again after the beep.

5.3Battery voltages and absorption time

5.3.1Set the voltage and timing threshold The programming is done in accordance with the following steps:

Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for minimum 2 seconds simultaneously.

With the Push Button 20 (select) select which of the battery level and of the absorption time have to be changed.

These four red LED’s show the function set:

Low voltage

LED 13

(ON/OFF)

Float charge

LED 12

(Batt. Low/high)

Absorption (End of charge)

LED 11

(Overload)

Equalization

LED 10

(Overtemp.)

Absorption Time

LED 10/11/12/13 (altogether)

XP-COMPACT V5.4

22/77

Page 20
Image 20
Studer Innotec Programming possible only with the remote control RCC-01, Standard setting, Reset value default settings