Studer Innotec SI SERIES Control, Safety, Internal fuse, Adjustments, Indicators, Standby Level

Models: SI SERIES

1 10
Download 10 pages 25.27 Kb
Page 5
Image 5
Adjustments

STUDER INNOTEC

SI

Adjustments

(Not automatic with Twinpower version)

Standby Level (1)

The activation of the inverter, when working in automatic mode, is dictated by the detection of a load. With this function, it is possible to adjust the minimum load detected between 0,3 and 20 Watts. This level is factory adjusted to 2 watts and so no further adjustment will probably be needed.

Adjustment procedure

Make sure that no device is connected.

Check for the presence of hidden users such as television, fax, video, … which often have a standby mode and remain working even after being turned off !

Put the switch in “ Autom. ” position.

Introduce a screw driver N°1 delicately in the hole (1) provided and turn gently until you feel the screw driver insert in the groove of the screw.

Turn clockwise Standby Level (1) until tight without pressing (do not force!).

Wait until the green LED blinks.

Activate the minimum charge you wish to detect.

Turn the screw slowly anti-clockwise Adjustment procedure without pressing until the inverter activates. (green LED illuminated).

Check that the inverter goes back to standby mode a couple of seconds after deactivation of all charges.

Warning : In maximum anti-clockwise position the inverter continues to work even if there is no load.

Control

The tension of the batteries is submitted to control. During their use, the tension must be between the following ranges :

11.4V and 16 V in the 12 Volt models,

22.8V and 32 V in the 24 Volt models,

45.6V and 61 V in the 48 Volt models.

Outside these ranges the inverter is automatically disconnected.

These values correspond to a no load situation and they are automatically adjusted according to the current of the battery.

The internal temperature and the maximum power are also submitted to control.

In the case of prolonged overload or deficient ventilation it is not possible to restart the inverter until it has cooled down.

Indicators

Green Run - LED (3)

Illuminated: the inverter is connected. A 230 V tension is present in the outlet.

Blinking : (only SI version) The inverter is in

Autom. ” mode and no voltage is detected by the standby system.

A 230 V tension is intermittently present!

Red Fault - LED (2)

The inverter is stopped :

The tension of the battery is not correct After an overload, overheating or short circuit To restart the inverter after a failure, put the switch (4) in “ OFF ” position for 10 seconds, then connect again.

Safety

The inverter is internally protected against overloads and short circuits. Should this protection fail, the inverter is equipped with a fuse (fire protection). If the fuse is broken, qualified technicians should control the installation and change the fuse.

Internal fuse

Fuse

Inverter SI (mod.)

40A

648

 

50A

624

- 1248

60A

824

– 1448

80A

612

– 2348 - 2360

100A

812

– 1224 – 3548 - 3060

2*100A

1212 – 1624 – 2324

2*125A

3324

The use of higher fuse value will not improve the performance of the inverter and will degrade safety protection !

User manual

SI V3.0 E

5

Page 5
Image 5
Studer Innotec SI SERIES Control, Safety, Internal fuse, Adjustments, Indicators, Standby Level, Adjustment procedure