STUDER INNOTECXP-COMPACT
9 Technical Data
Model | XPC1112 |
| XPC1624 |
| XPC1648 | ||
Inverter |
|
|
|
|
|
| |
Nominal battery voltage | 12 V |
|
| 24 V |
| 48 V | |
Input voltage range | 9.5 – 17 V |
| 19 – 34 V |
| 38 – 68 V | ||
Nominal power | 1100 W |
| 1600 W |
| 1600 W | ||
Maximum power load 30 min. P30 | 1400 W |
| 2200 W |
| 2000 W | ||
Maximum power load 5 sec |
|
| 3 x Pnom |
|
| ||
Maximum load |
|
| up to short circuit | ||||
Maximum asymmetric load |
|
| up to Pnom |
|
| ||
Standby adjustment |
|
| 1 to 25 W |
|
| ||
Cos ϕ |
|
|
| 0.1 - 1 |
|
| |
Maximum efficiency | 94 % |
|
| 95 % |
| 95 % | |
Consumption OFF/Standby/ON | 0.5 / 0.6 / 4 W |
| 0.8 / 0.9 / 7 W |
| 1.2 / 1.3 / 7 W | ||
Output voltage |
| 230 Vac | (- 10% / 0) | ||||
Output frequency crystal controlled |
|
| 50 Hz ± 0.05 % |
|
| ||
Total harmonic distortion | < 4% |
|
|
| < 2% | ||
Dynamic behaviour on load change 0 → 100 % |
|
|
| 0.5 ms |
|
| |
Overload and short circuit protection | Automatic disconnection with 3 time restart attempt | ||||||
Overheat protection | Acoustic warning before | ||||||
Battery charger (4 STEP) |
|
|
| ||||
Charging current adjustable | 0 – 45 A |
| 0 – 37 A |
| 0 – 20 A | ||
Maximum input voltage |
|
| 265 Vac |
|
| ||
Minimum input voltage | Adjustable threshold from 150 to 230 Vac | ||||||
Input frequency |
|
| 45 – 65 Hz |
|
| ||
Power Factor Correction (PFC) |
|
| EN |
|
| ||
Optional solar charger (4 stages) |
|
|
|
|
|
| |
Maximum PV open circuit voltage (V) | 25 V |
|
| 45 V |
| 90 V | |
Maximum charge current (A) | 30 A |
|
| 30 A |
| 20 A | |
Working principle: | Shunt |
|
| Shunt |
| Shunt | |
Battery control (thresholds and times adjustable by the user, only with | |||||||
Absorption time |
|
|
|
|
| ||
End charge cycle voltage | 14.4 V |
|
| 28.8 V |
| 57.6 V | |
Floating voltage | 13.6 V |
|
| 27.2 V |
| 54.4 V | |
Equalisation voltage | 15.6 V |
|
| 31.2 V |
| 62.4 V | |
10.8 V |
|
| 21.6 V |
| 43.2 V | ||
Temperature compensation (optional |
|
|
|
| |||
General data |
|
|
|
|
|
| |
Multifunction contact - potential free (3 points) |
|
| 16 A – 250 Vac |
|
| ||
Max. current on transfer relay | 16A / 3.5 kVA |
| 16A / 3.5 kVA |
| 16A / 3.5 kVA | ||
Transfer time |
|
| < 20 ms |
|
| ||
Weight | 11.7 kg |
| 12.6 kg |
| 12.6 kg | ||
Dimension h x l x L [mm] | 124 / 215 / 410 |
| 124 / 215 / 410 |
| 124 / 215 / 410 | ||
IP protection index |
| IP | 20 / IP 23 with top cover | ||||
EEC conformity | EN50081 I/II, EN 55014 – EN 55022, EN | ||||||
IEC 801 I/II/III/IV, IEC | |||||||
| |||||||
Working range |
|
|
|
|
| ||
Ventilation | from 45°C |
|
|
|
|
| |
Acoustic level without / with ventilation | < 10 dB / < 35 dB |
|
|
|
|
| |
Warranty | 2 years |
|
|
|
|
| |
Options |
|
|
|
|
|
| |
Solar charger |
|
|
|
|
| ||
Remote control (112 x138 x 25mm / 20 m cable) |
|
|
|
|
| ||
C- IP23 |
|
|
|
|
| ||
AC cable cover |
|
|
|
|
| ||
Battery temperature sensor |
|
|
|
|
| ||
(58 x 51.5x 22mm / 3 m cable) |
|
|
|
|
|
| |
Data may change without any notice |
|
|
|
|
|
|
User manual |