APPLIANCE SPECIFICATIONS

5 ³⁄₄"

4"

(146 mm)

(102 mm)

 

 

 

7 ¹⁄₄"

 

 

 

(184 mm)

 

 

 

 

36"

 

 

33 ¹⁄₂"

(914 mm)

(851 mm)

20¹⁄₄"

(514 mm)

1"

(25 mm)

6"

(152 mm)

38"

(965 mm)

Front

Appliance Top

Spacer

 

 

 

 

9 ¹⁄₄"

 

 

 

Combustion

(235 mm)

 

6 ¹⁄₄"

 

Air Inlet

 

 

(159 mm)

33 ¹⁄₂"

 

 

 

 

(851 mm)

 

5"

 

 

 

32"

 

 

 

(813 mm)

(127 mm)

 

 

 

 

 

 

 

2"

 

2 ¹⁄₂"

9 ⁵⁄₁₆"

2 ¹⁄₂"

(51 mm)

 

(64 mm)

(238 mm)

(64 mm)

 

Junction Box

Alternate Gas

6 ¹⁄₄"

Gas Line

 

Line Access

Access

 

 

(159 mm)

 

 

 

 

 

 

14"

 

14"

 

(356 mm)

 

(356 mm)

 

Left Side

 

Right Side

 

4 ⁵⁄₈"

28 ³⁄₁₆"

 

 

(118 mm)

(716 mm)

 

14"

(356 mm)

Appliance

Top Spacer

38"

(965 mm)

Top View

Figure 2

4

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Venting

Gas Vent Rule – Gas vent caps are not permitted within 8 feet (2.4 mm) of a vertical wall or similar obstruction. Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with Table 1 (Figure 3 ), provided that in no case shall any discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA 54) 7.6.2) (CAN/CGA B149).

X

12

Roof Pitch is X/12

Minimum Height from Roof to Lowest Discharge Opening

Figure 3

 

Minimum Height

Roof Slope

from Roof to Lowest

Discharge Opening

 

 

 

 

 

Feet

Meters

Flat to 6/12

1' 0"

0.3

Over 7/12 to 9/12

2' 0"

0.6

Over 10/12 to 12/12

4' 0"

1.2

Over 13/12 to 16/12

6' 0"

1.8

 

 

 

Over 17/12 to 21/12

8' 0"

2.4

 

 

 

Note: Venting terminals shall not be recessed into a wall or siding.

Table 1

Multiple Terminations – These appliances may vent adjacent to and at the same level with any other gas appliances (including direct-vent appliances) provided that there is at least 2 ft. (0.6m) between the proximal edges of the vent caps. These appliances may be vented adjacent to a chimney vent servicing a solid fuel fireplace provided the B-vent cap is at least 2 ft. (0.6m) away from the nearest point of the chimney opening.