INTRODUCTION
General Information
These fireplaces are conventional heat circulat- ing appliances with standard grates, outside combustion air kit and standard decorative glass doors. The BCD36MH model is fitted with a blower and is available as an option for model BC36MH.
The grate included properly positions the fire and limits the amount of fuel. IF A REPLACEMENT
GRATE IS NEEDED REPLACE THE GRATE WITH MODEL 87L20 ONLY.
Note: Illustrations shown reflect “typical” installations with nominal dimensions and are for design and framing reference only. Actual installations may vary due to individual design preferences. However, always maintain minimum clearances to combustible materials and do not violate any specific installation requirements.
These fireplaces have been tested and listed by Warnock Hersey (Report No. J99025865A) to U.L. standard 127. These units are intended for installation in manufactured homes. These units may also be installed in buildings of con- ventional construction including commercial, providing all instructions provided herein are strictly adhered to.
These fireplace systems are designed for in- stallation in accordance with the National Fire Protection Standard for chimneys, fireplaces and solid fuel burning appliances; NFPA 211- latest edition and in accordance with codes such as the BOCA Basic/National Codes, the Standard Mechanical Code and the Uniform Building Codes.
TYPICAL |
|
|
INSTALLATION |
| |
Chimney and | Firestop | |
Termination |
| |
|
| Thimble |
Figure 1 | Outside Combustion Air Kit | |
|
WARNING
Failure to use manufacture provided parts, variations in techniques and construction materials or practices other than those described in this manual may create a fire hazard and void the limited warranty.
WARNING
Do not pack or fill required air spaces with insulation or other material. No material is allowed in these areas. Secure the airspace around the chimney with the firestop/thimble before completing the installation. Maintain 1" clearance between chimney and thimble.
WARNING
If insulation is used, the fireplace must not be placed directly against it. Insulation or vapor barriers, if used, must first be covered with gypsum board, plywood, particle board or other material to assure insulation and vapor barriers remain in place.
When complete these fireplace systems con- sists of four basic
1.The Fireplace
2.The Chimney and Termination
3.Glass Doors
4.Combustion Air Kit
CLEARANCES AND HEIGHT
REQUIREMENTS
The fireplace may be placed on or near normal construction materials*. The combustion air kit, firestop spacer and roof flashing (not chase flashings) may be placed directly on or against normal construction materials.* The chimney and fireplace outer wrapper require a minimum 1" air space to insulation and building materi- als. A combustible mantel may be installed 12" above the opening of the fireplace as per NFPA
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
The minimum installed height of the completed fireplace system is 10' 6". The maximum height is 40' 0". See the Chimney Height section on Page 3 for more information.
The fireplace and chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it. This is important to pre- vent possible personal injury or fire hazard.
For questions, please call your distributor or the manufacturer. Special restrictions apply to the front and facing of the fireplace and nearby walls (See Pages 16 and 17).
CHIMNEY SYSTEM
These fireplaces are designed and code listed for use with Security Chimneys FTF8 chimney sys- tem only. Always use Security Chimneys FTF8 chimney components with these fireplaces. Do not modify or alter these components as this may cause a potential serious hazard and void the Warranty.
*Construction Materials:
• Framing Materials • Paneling
• Particle Board | • Flooring |
• Dry Wall | • Plywood |
•Noncombustible Insulating Materials
•Etc.
Chimney Height
The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 40' and must also meet minimum height requirements. Refer to the minimum system height chart.
Minimum System Height
Security's FTF8 Pipe
Vertical Installation | 10' 6" |
One Offsets | 12' 0" |
|
|
Two Offsets | 25' 0" |
|
|
Table 1
3