ASSEMBLY STEPS

Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence.

1.Position firebox prior to framing or into prepared framing.

2.Install the chimney system.

3.Connect house wiring to the fireplace for blower (blower is optional for model BC36MH).

4.Install the outside combustion air kit.

5.Plumb gas line if a decorative gas appliance will be used. (Gas connections should only be performed by an experienced, licensed/ certified tradesman).

6.Complete the installation, finish wall mate- rial, surround and hearth extension to your individual taste.

Study the three dimensional illustration (Figure 1) to get a general idea of each element of your fireplace system.

PRE-INSTALLATION NOTES

The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place fireplace on carpeting, vinyl or other soft floor coverings. It may, however, be placed on flat wood, plywood, particle board or other hard surfaces. Be sure fireplace rests on a solid continuous floor or platform with appropriate framing for support and so that no cold air can enter the room from under the fireplace.

The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.

Usually, no special floor support is needed for the fireplace, however, to be certain:

1.Estimate the total weight of the fireplace system including chimney and surround materials such as brick, stone, etc., to be installed. Shipping weights for the fireplace may be found on Page 7.

2.Measure the square footage of the floor space to be occupied by the system, surrounds and hearth extensions.

3.Note the floor construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of floor boards.

4.Use this information and consult your local building code to determine if you need ad- ditional support.

CAUTION

Do not block the heat-circulating air inlet and outlet ports. Doing so may result in a potential fire hazard.

CAUTION

The structural integrity of the manufactured home floor, wall, ceiling and roof must be main- tained.

The firestop thimble supplied with the unit must be used on a manufactured home installation. The firestop thimble must extend completely though the roof cavity to the outermost plane of the roof (See Figures 16, 17 and 18). Maintain 1" clearance between the thimble and the chimney.

If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.

CLEARANCES

Minimum clearance to combustibles for the appliance is as follows: sides and back - 1" (25 mm), floor - 0" (0 mm), adjacent wall - 12" (305 mm), ceiling - 37-1/2" (953 mm).

INSTALLING THE FIREPLACE

IMPORTANT: Plated polished brass glass doors may have a plastic covering over all brass pieces for protection during shipping and handling. The plastic covering should be removed after installation of the fireplace before its use. Under the plastic covering is a protective lacquer coating which should not be removed. In some instances, if it is removed, irreversible damage to the brass finish could occur.

Step 1. Slide the fireplace into prepared framing or position fireplace in its final position and frame later.

The fireplace may not be recessed into a combustible floor. Maintain the floor to hearth clearance established by the fireplace lower front face.

Step 2. Insert the provided metal safety strips, beneath the fireplace as illustrated (Figures 6 through 9). The safety strips should overlap 1/2" for continual coverage of the floor.

Note: Safety strips are not required when fire- place rests on a noncombustible surface.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

 

Top Spacer

 

Maintain

 

1" (25 mm)

 

Air Space

 

At Back

 

And Sides

 

Hearth

1" (25 mm) Space

Extension

 

Metal Safety Strip

Floor

Note: Hearth extensions must not interfere with

circulating grillwork

 

Figure 6

 

 

 

Maintain

 

 

1" (25 mm)

 

 

Air Space

 

 

At Back

 

 

And Sides

 

 

Hearth

1" (25 mm) Space

Extension

 

Metal Safety Strip

Platform

Floor

Note: Hearth extensions must not interfere with

circulating grillwork

 

Figure 7

 

 

Note: Install the hearth extension only as il- lustrated (see Pages 16 through 18).

The safety strips should extend from front of the fireplace at least 1-1/2" and should extend to be at least flush with the sides. In the event a wooden support is used to elevate the fireplace above the floor, a “Z” type safety strip should be fabricated and used to protect the front surface of the wood support as well as the floor beneath the hearth extension (Figures 8 and 9). The safety strips should be tacked down to prevent possible movement.

Note: The “Z” type safety strip is not sup- plied.

5

Page 5
Image 5