4

3.Add the BTU/Hr of all the fuel burning appli- ances in the space.

Vent-Free heater

 

_______

BTU/Hr

Gas appliance #1*

 

_______

BTU/Hr

Gas appliance #2

+ _______

BTU/Hr

Total = _______

BTU/Hr

Example:

 

 

 

VFST Vent-free heater

32,000

BTU/Hr

Gas appliance #1

 

34,000

BTU/Hr

(water heater)

 

 

 

Total =

66,000

BTU/Hr

*Do not include direct-vent gas appliances. Direct-vent is sealed combustion and draws combustion air from the outdoors.

4. Compare the maximum BTU/Hr the space can support with the actual amount of BTU/ Hr used.

_________

BTU/Hr

 

(max. the space can support)

_________

BTU/Hr

 

(actual amount of BTU/Hr used)

Example:

 

40,960

BTU/Hr

 

(max. the space can support)

66,000

BTU/Hr

 

(actual amount of BTU/Hr used)

The space in the above example is a confined space because the actual BTU/Hr used is more than the maximum BTU/Hr the space can sup- port. You must provide additional fresh air.

WARNING: IF THE AREA IN WHICH THE HEATER MAY BE OPERATED IS SMALLER THAN THAT DEFINED AS AN UNCON- FINED SPACE, PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR BY ONE OF THE METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1 1992, SECTION 5.3 OR APPLI-

CABLE LOCAL CODES.

Your options are:

a. Rework equations adding the space of ad- joining room(s). If the extra volume provides an unconfined space, then remove door or add ventilation grills between rooms. Refer to National Fuel Gas Code, ANSI Z223.1 1992, Section 5.3.

b. Vent room directly to the outdoors. Refer to National Fuel Gas Code, ANSI Z223.1 1992, Section 5.3.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, then the space is an unconfined space. You will need no additional fresh air ventilation for an unconfined space.

LOCATION OF FIREPLACE

Carefully select the best location for installa- tion of your VFST or VFPF series Unvented Room Heater. The following factors should be taken into consideration:

Clearance to side wall, ceiling, woodwork and windows.

Location must not be affected by drafts caused by kitchen exhaust fans, return air registers for forced air furnaces/air condition- ers, windows or doors.

Installation must provide adequate ventila- tion and combustion air.

Do not install the VFST or VFPF series heat- ers in a sleeping room or bathroom.

Never obstruct the front opening of the heater or restrict the flow of combustion and ventilation air.

This appliance may be installed in an after- market* manufactured (Mobile) Home, where not prohibited by state or local codes.

*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.

Minimize modifications to existing con- struction.

To ensure even heat distribution, it is best to position the heater centrally within the rooms. Make sure there is adequate ventilation where the heater is installed. The gas appliance will shut off if the oxygen level falls below 18%.

These appliances are uniquely suited for in- stallations requiring a utility shelf positioned directly above the fireplace. Utility shelves like these are commonly used for locating televi- sion sets and decorative plants.

To provide for the lowest possible shelf sur- face, combustible materials used to support a utility shelf directly above these appliances should be positioned just above the appliance top spacers. The minimum height from the base of the appliance to the underside of com- bustible materials used to construct a utility shelf is 43 ¹⁄₄” (1099 mm).

The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom sur- face must be used.

If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.

WARNING: MAINTAIN MINIMUM CLEARANCES.

Do not install in the vicinity of gasoline or other flammable liquids. The heater must be kept clear and free from these combustible materi- als and may not be located near where they are stored.

Clearances

WARNING: DO NOT INSTALL VFST SE- RIES UNVENTED ROOM HEATERS IN SLEEPING QUARTERS, OR IN RECRE- ATIONAL VEHICLES.

WARNING: DO NOT INSTALL THE VFST UNVENTED ROOM HEATER:

WHERE CURTAINS, FURNITURE, CLOTHING OR OTHER FLAMMABLE OBJECTS ARE LESS THAN 42" FROM THE FRONT OF THE UNVENTED ROOM HEATER.

IN HIGH TRAFFIC AREAS.

IN WINDY OR DRAFTY AREAS.

Ensure the minimum clearances shown in Fig- ures 1 and 2 are maintained.

Combustible mantles may be installed above the appliance (as shown in Figure 2 ). The mantle projection may be extended beyond 8" if the height above the firebox opening is in- creased proportionately as detailed by the in- crements shown.

Page 4
Image 4
Superior VFST-CMP-2 Cable Local Codes, Location of Fireplace, Clearances, High Traffic Areas Windy or Drafty Areas

VFPF-CMP-2, VFPF-CMN-2, VFST-CMN-2, VFST-CMP-2 specifications

The Superior VFST-CMP-2, VFPF-CMN-2, VFPF-CMP-2, and VFST-CMN-2 represent a cutting-edge suite of products designed to meet the demands of modern applications in various industries, including telecommunications, data management, and industrial automation. Each of these models incorporates advanced features and technologies aimed at enhancing performance, reliability, and user experience.

The VFST-CMP-2 is particularly focused on high-speed data processing. With an impressive throughput and low latency, it is engineered for tasks that require rapid data handling, making it suitable for applications in cloud computing and data centers. This model incorporates state-of-the-art error correction algorithms, ensuring data integrity during transmission and significantly reducing downtime.

In contrast, the VFPF-CMN-2 is tailored for network management and monitoring. It boasts a comprehensive interface that allows users to track network performance in real-time. The intuitive dashboard provides insights into traffic loads, bottlenecks, and overall system health. This model is equipped with cutting-edge analytics features that leverage machine learning to predict potential issues before they become critical, enhancing proactive maintenance capabilities.

The VFPF-CMP-2 combines features from both offerings, positioned as a hybrid solution that caters to versatile applications. It balances powerful data processing and efficient network management, making it an optimal choice for organizations looking to streamline operations across various platforms. With its modular architecture, users can easily scale their systems as demand increases without significant overhauls.

Finally, the VFST-CMN-2 excels in interoperability. Designed to integrate seamlessly with existing infrastructures, it supports a wide range of protocols and standards. This flexibility ensures that it can be deployed in diverse environments, minimizing compatibility issues. The device also emphasizes security, incorporating advanced encryption technologies to protect sensitive data during transmission.

In summary, the Superior VFST-CMP-2, VFPF-CMN-2, VFPF-CMP-2, and VFST-CMN-2 are exemplary models that bring together innovative features and technologies. Their unique characteristics make them well-suited for various applications, providing essential tools for enhanced data processing, network management, and operational efficiency. Organizations investing in these products are poised to benefit from improved performance and adaptability in an ever-evolving technological landscape.