INSTALLATION AND MAINTENANCE INSTRUCTIONS

1400 Direct Wire Ionization Smoke Detector

3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com

Specifications

 

 

Diameter:

5.5 inches (140 mm)

Height:

3.12 inches (80 mm)

Weight:

0.7 lb. (310 g)

Operating Temperature:

0°C to +49°C (32°F to 120°F)

Latching Alarm:

Reset by momentary power interruption.

Operating Humidity:

10% to 93% Relative Humidity, Noncondensing

Electrical Ratings:

 

 

System Voltage:

12/24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 µA Maximum

Standby Ratings:

8.5

VDC Minimum

 

35 VDC Maximum

 

100 µA Maximum

Alarm Ratings:

4.2

VDC Minimum at 10 mA

 

6.6

VDC Minimum at 100 mA

 

Alarm current must be limited to 100 mA maximum by the control panel. If used, the

 

RA400Z Remote Annunciator operates within the specified detector alarm currents.

Reset Voltage:

2.5

VDC Minimum

Reset Time:

0.3

S Maximum

Start-up Time:

35 S Maximum

 

 

 

Before Installing

Please thoroughly read the System Sensor manual A05- 1003, Applications Guide for System Smoke Detectors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installation in Canada, refer to CAN/ULC- S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)

General Description

System Sensor 1400 dual-chamber ionization smoke detec- tors utilize state-of-the-art, unipolar sensing chambers. These detectors are designed to provide open area protec- tion, and to be used with compatible UL-listed, 2-wire con- trol panels only. The detector’s operation and sensitivity can be tested in place.

Each detector includes an LED that provides a local visual indication of the detector’s status. The LED blinks every ten seconds as an indication that power is applied to the detector and lights continuously in alarm. These detectors also have the latching alarm feature. The alarm can be reset only by a momentary power interruption.

The detector also has provision for the connection of an optional Model RA400Z Remote Annunciator. The RA400Z provides a visual indication of an alarm and mounts to a single gang box.

Spacing

NFPA 72 defines the spacing requirements for smoke detectors. Typically, this is 30 feet when the detectors are installed on a smooth ceiling. However, ALL installations must comply with NFPA 72 and/or special requirements of the authority having jurisdiction.

D400-07-00

1

I56-279-05R

Page 1
Image 1
System Sensor 1400 specifications Specifications, Before Installing, General Description, Spacing

1400 specifications

The System Sensor 1400 series is an advanced line of smoke detectors designed to enhance safety in commercial and industrial settings. Known for its reliability and precision, the 1400 series employs cutting-edge technologies to ensure early detection of smoke and fire, thus providing crucial time for evacuation and response.

One of the main features of the System Sensor 1400 is its dual-sensor technology, which combines both photoelectric and ionization detection methods. This dual approach allows the detector to identify a wide range of smoke particles generated from various types of fires, from fast-flaming fires to smoldering ones. This versatility significantly reduces the chances of false alarms while maintaining a high level of sensitivity.

Another key technological advancement in the 1400 series is its built-in communication capabilities. The detectors can be integrated into larger fire alarm systems, allowing for remote monitoring and real-time alerts. This integration is facilitated by the use of an advanced communication protocol that enables quick data transmission and reduces response times in emergencies.

The System Sensor 1400 series also features a robust design that ensures durability and reliability. Constructed from high-quality materials, these detectors are resistant to environmental factors such as humidity and temperature fluctuations. This makes them suitable for a variety of settings, including warehouses, manufacturing plants, and commercial buildings.

In addition, the 1400 series incorporates a user-friendly interface that simplifies installation and maintenance. The detectors are equipped with LED indicators that provide visual alerts for operational status, including power, alarm, and trouble signals. This allows maintenance personnel to quickly assess the detector’s functionality and perform necessary checks or replacements.

Ease of installation is further enhanced by the use of a universal mounting bracket, which simplifies the setup process and reduces downtime. The series is also designed to accommodate various power options, including battery backup, ensuring continued operation even during power outages.

In conclusion, the System Sensor 1400 series stands out as a premier choice for smoke detection in commercial and industrial applications. Its combination of dual-sensor technology, robust design, seamless integration capabilities, and user-friendly features makes it a reliable solution for enhancing fire safety and protection in any environment.