INSTALLATION AND MAINTENANCE INSTRUCTIONS
1400 Direct Wire Ionization Smoke Detector
3825 Ohio Avenue, St. Charles, Illinois 60174
Specifications |
|
|
Diameter: | 5.5 inches (140 mm) | |
Height: | 3.12 inches (80 mm) | |
Weight: | 0.7 lb. (310 g) | |
Operating Temperature: | 0°C to +49°C (32°F to 120°F) | |
Latching Alarm: | Reset by momentary power interruption. | |
Operating Humidity: | 10% to 93% Relative Humidity, Noncondensing | |
Electrical Ratings: |
|
|
System Voltage: | 12/24 VDC | |
Maximum Ripple Voltage: | 4 Volts peak to peak | |
0.02 µA Maximum | ||
Standby Ratings: | 8.5 | VDC Minimum |
| 35 VDC Maximum | |
| 100 µA Maximum | |
Alarm Ratings: | 4.2 | VDC Minimum at 10 mA |
| 6.6 | VDC Minimum at 100 mA |
| Alarm current must be limited to 100 mA maximum by the control panel. If used, the | |
| RA400Z Remote Annunciator operates within the specified detector alarm currents. | |
Reset Voltage: | 2.5 | VDC Minimum |
Reset Time: | 0.3 | S Maximum |
35 S Maximum | ||
|
|
|
Before Installing
Please thoroughly read the System Sensor manual A05- 1003, Applications Guide for System Smoke Detectors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installation in Canada, refer to CAN/ULC- S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
General Description
System Sensor 1400
Each detector includes an LED that provides a local visual indication of the detector’s status. The LED blinks every ten seconds as an indication that power is applied to the detector and lights continuously in alarm. These detectors also have the latching alarm feature. The alarm can be reset only by a momentary power interruption.
The detector also has provision for the connection of an optional Model RA400Z Remote Annunciator. The RA400Z provides a visual indication of an alarm and mounts to a single gang box.
Spacing
NFPA 72 defines the spacing requirements for smoke detectors. Typically, this is 30 feet when the detectors are installed on a smooth ceiling. However, ALL installations must comply with NFPA 72 and/or special requirements of the authority having jurisdiction.