System Sensor BS5839 Addressing Methods, Dedicated address programmer, Decimal address switches

Models: BS5839

1 32
Download 32 pages 58.43 Kb
Page 5
Image 5

Alarm Signal if appropriate

Status of module output

Remote test status

Manufacturer code

Most commonly, each device on the loop will be polled in turn, however to increase speed around a loop, some protocols allow polling of groups of devices on a single communication.

Note that since different manufacturers have their own protocols, it is important to ensure compatibility between the detectors and control panel you intend to use. Some detector manufacturers produce intelligent detectors with different communication protocols for different customers, so two detectors which look virtually identical in appearance may not be compatible. Always check with the manufacturer of the control panel.

1.4. ADDRESSING METHODS

Different manufacturers of intelligent systems use a number of different methods of setting the address of a device, including:

7-bit binary or hexadecimal DIL switch

only from one end. If the loop is broken (See figure 1.5.1.), the panel will detect the loss of communications with the detectors beyond the break, signal a fault, and switch to drive the loop from both ends. The system therefore remains fully operational, and can possibly even indicate the area of the break.

In order to give tolerance against short circuits on the loop, short circuit isolators are placed at intervals on the loop. Should a short circuit occur on the loop (Figure 1.5.2.) the isolators directly on either side of the fault will isolate that section. The panel will detect the loss of the devices, signal a fault and drive the loop from both ends, thereby enabling the remainder of the loop to operate correctly and ensuring minimum loss of coverage.

Short circuit isolators are available as separate modules and incorporated into a detector base.

Some products, for example System Sensor’s M200 Series modules, have isolators built into each of the loop devices. With this configuration, since only the section of wiring between the two adjacent devices is isolated there will be no loss of coverage should a short circuit occur.

Intelligent Fire Alarm Systems

Dedicated address programmer

Automatic, according to physical position on the loop

Binary ‘address card’ fitted in the detector base

Decimal address switches

System Sensor’s Series 200 plus range of intelligent devices uses decimal address switches to define a device’s address between 00 and 99 (See Figure 1.4.1). This is a simple intuitive method, not requiring knowledge of binary or purchase of specialised equipment to set addresses.

24V

SYSTEM FAULT: OPEN CIRCUIT:

Zone 2 Module 01

FIRST FLOOR CANTEEN

SYSTEM OK

FIRE ALARM

FAULT

SYSTEM RESET

INTELLIGENT

FIRE ALARM

CONTROL PANEL

24V

Line break

Panel detects the loss of devices after the break, signals a fault and powers from both ends of the loop to retain full coverage.

3

4

5

6

3

4

5

6

Figure 1.5.1. Open Circuit Fault

Isolating

Impedance

2 7 2 7

1

0

9

8

1

0

9

8

TENSUNITS

Figure 1.4.1 System Sensor decade address switches

-Address 03 selected

24V

 

SYSTEM FAULT: SHORT CIRCUIT:

 

Zone 2 DETECTOR 03

 

FIRST FLOOR CANTEEN

 

SYSTEM OK

 

FIRE ALARM

 

FAULT

 

SYSTEM RESET

Short Circuit

 

INTELLIGENT

 

FIRE ALARM

 

CONTROL

 

PANEL 24V

 

Isolators on either side of the short circuit switch an impedance onto the line to isolate it.

Devices between the two isolators are lost, however the remainder of the circuit still operates correctly.

Isolators automatically reset the line when the short circuit is removed

Differences in the protocol between detectors and modules allow them to have the same address without interfering with each other, and normally address 00 (the factory default setting) is not used within a system so that the panel can identify if a device address has not been set: Hence a total of up to 198 devices - 99 detectors and 99 modules (including call points, sounders, input and output modules) may be connected to a loop.

1.5. SYSTEM FAULT TOLERANCE

Due to the looped wiring method used for analogue systems, they are more tolerant to open and short circuit wiring faults than conventional systems.

Under normal conditions, the loop will typically be driven

Isolating

Impedance

Figure 1.5.2. Short Circuit Fault

Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.

Reference must be made to relevant national and local standards.

5

Page 5
Image 5
System Sensor BS5839 Addressing Methods, Dedicated address programmer, Binary ‘address card’ fitted in the detector base

BS5839 specifications

System Sensor BS5839 is a standard that pertains to fire detection and alarm systems, providing guidelines for the design, installation, and maintenance of these essential safety tools. It is crucial for safeguarding lives and property, ensuring that fire detection systems are effective and reliable. The BS5839 standard, established in the UK, covers a wide range of fire alarm system types, including conventional, addressable, and wireless systems.

One of the main features of BS5839 is its comprehensive classification of fire detection systems. The standard divides systems into categories based on the level of risk and the environment in which the system will operate. This classification helps ensure that the system installed meets the specific needs of the building and its occupants. For example, Category L systems are meant for life safety, while Category P systems are designed to protect property.

The technologies underpinning BS5839 include various types of detectors, alarm devices, and control panels. Smoke detectors, heat detectors, and multi-sensor detectors are prominent among the devices specified in the standard. Smoke detectors use photoelectric or ionization principles to detect smoke and signal an alarm, while heat detectors respond to temperature changes. Multi-sensor detectors combine both smoke and heat detection technologies to provide a more reliable response to fire conditions.

Another key characteristic of BS5839 is the emphasis on regular testing and maintenance. The standard outlines procedures to ensure that systems remain operational and effective over time. This includes routine system checks, functional testing, and more in-depth inspections at regular intervals. Ensuring that systems are maintained according to BS5839 is vital for compliance with insurance requirements and for safeguarding against potential legal liabilities.

Furthermore, BS5839 highlights the importance of staff training and awareness. It emphasizes that personnel responsible for fire safety must be adequately trained in the operation and response to fire alarm systems. This ensures that in the event of a fire, occupants are prompted to take appropriate action and evacuate safely.

In summary, System Sensor BS5839 provides a crucial framework for fire detection and alarm systems. Its classification of systems, incorporation of advanced technologies, and emphasis on maintenance all contribute to enhanced safety and compliance, protecting lives and property effectively.