6Note: This document is based on the recommendatio ns of BS5839 Part 1: 2002. I t is intended only as a guide to the ap plication of fire detection systems.
Reference must be made to relevant national and local stan dards.
1.6. DRIFT COMPENSATION AND MAINT ENANCE ALARM
The sensitivity of a smoke detector t ends to change as it
becomes contaminated with dirt or du st (see figure 1.6.1). As
contamination builds up, it usually become s more sensitive,
leading to the risk of a false alarm, but in some ca ses can
become less sensitive, so delaying the alarm if a fir e is
detected. To counter this, if a detector drif ts outside its
specification, a maintenance signal may be se nt to the panel
warning that the detector needs cleaning.
To further increase the maintenance inter val, many systems
incorporate a “drift compensatio n” function, included in either
the detector or the control panel algo rithms. These functions
use algorithms that monitor the sensiti vity of a detector, and
modify its response to compensate f or a build up of dust in
the chamber over time. Once the detector reac hes the “drift
limit” when the dirt build up can no longer be comp ensated
for, a fault can be signalled. Some systems also incor porate
a warning to signal that a detector is approac hing its
compensation limit and requires cleaning.
Figure 1.6.1 Chamber Contamination and Drift
Compensation
1.7. PRE-ALARM FACILITY
One advantage of intelligent type sys tems is that since the
data sent by a detector to the panel varies wi th the local
environment, it can be used to detect wh en the device is
approaching an alarm condition. This “Pr e-Alarm” can be
signalled at the panel and can therefore be inve stigated to
check if there is a real fire, or if it is caused by oth er signals,
for example steam or dust from building work . This can
avoid the inconvenience and expense of evacuating a buil ding
or calling out the fire brigade unnecessarily b ecause of a
nuisance alarm. The Pre-Alarm Thr eshold is typically set at
80% of the alarm threshold.
1.8. FIRE ALARMS
When a fire is detected, the control pan el indicates an alarm
by activating the fire indicator for the rele vant zone on the
control panel, sending a command to the relevan t detector
to illuminate its LED and activate alarm sig nals to start
evacuation. Most intelligent fire system c ontrol panels include
alphanumeric displays enabling them to show info rmation
on the source of the alarm. This may simply be a zone an d
detector address, or could be more desc riptive for example
“Smoke Detector, Bedroom 234”. The control panel may a lso
use control modules to operate additio nal electrical equipment
such as air conditioning units and door rele ases to prevent the
spread of smoke and fire.
The alarm signals can either be a zone of convent ional
sounders and strobes activated vi a control modules on the
loop or directly from the control pan el, or addressable loop
powered devices connected on the same loop a s the detectors
and activated by direct command from the p anel. Loop
powered sounders tend to have lower wiring cost s, however
the number permissible on the loop may be restr icted by
current limitations.
On larger sites, it may be desirable to use zoned a larms. This
allows a phased evacuation to be carried out , with areas
at most immediate risk being evacuated first , then less
endangered areas later.
1.9. FIRE SYSTEM ZONES
Conventional fire alarm systems group de tectors into
‘zones’ for faster location of a fire, with a ll the detectors in
a particular zone being connected on one cir cuit. Although
intelligent systems allow the precise device t hat initiated an
alarm to be identified, zones are still used i n order to make
programming the system and interpret ing the location of a fire
easier. The control panel will have individual fire indi cators
for each zone on the system, and the control p anel response
to an alarm is often programmed accor ding to the zone of the
device in alarm rather than its individua l address.
Whilst the division of a loop into zones is achieve d within the
panel software, BS5839 p art 1 recommends that a single
wiring fault in one zone should not affect t he operation
of the system in other zones of the building. To meet this
recommendation, a short circuit isola tor should be placed on
each boundary between zones (fig ure 1.9.1). In this instance,
a short circuit in one zone would cause the isol ators on either
side of the zone to open, thereby disabling that zo ne. Any
devices in neighbouring zones would be protec ted by the short
circuit isolators and remain operati onal.
Figure 1.9.1 Intelligent System Fire Zones
Intelligent Fire Alarm Systems
ChamberValue
Time
Clean Air
Value Uncompensated
AlarmThreshold
Uncompensated
ChamberValue Compensated
Threshold
Smoke required to
reach alarm
threshold reduces -
Detector sensitivity
increases
Threshold
increased to
compensate for
increased chamber
clean air value.
ISOLATOR
ISOLATOR
ISOLATOR
Zone 1
Zone 2
Zone 3
Zone 4
INTELLIGENT
FIRE ALARM
CONTROL
PANEL
FIREALARMSYSTEMOK
28January2003
12:15pm
SYSTEM OK
SYSTEM RESET
FIRE ALARM
FAULT